Piping installation
Installer and user reference guide
80
Pattern 1
a
b
a
b
a
b
a To indoor unit
b Piping between outdoor units
NOT allowed (oil remains in piping)
Allowed
To avoid the risk of oil retention to the outmost outdoor unit, always connect the
stop valve and the piping between outdoor units as shown in the 4 correct
possibilities of the figure below.
a
b
b
a
b
b
a
a
b
a
a
a To indoor unit
b Oil collects to the outmost outdoor unit when the system stops
NOT allowed (oil remains in piping)
Allowed
If the piping length between the outdoor units exceeds 2  m, create a rise of
200 mm or more in the gas line within a length of 2 m from the kit.
If
≤2 m
a
b
b
a
b
b
a
Then
b
≤2 m
Pattern 2
a
b
a
b
a a
b
RXMLQ8 + RXYLQ10~14T7Y1B*
VRV IV system air conditioner
4P543427-1A – 2020.10