Daikin VRV IV Installer And User Reference Manual page 107

System air conditioner
Hide thumbs Also See for VRV IV:
Table of Contents

Advertisement

RXMLQ8 + RXYLQ10~14T7Y1B*
VRV IV system air conditioner
4P543427-1A – 2020.10
INFORMATION
Multi units are standard combinations.
Model
RXMLQ8
RXYLQ10
RXYLQ12
RXYLQ14
RXYLQ16
RXYLQ18
RXYLQ20
RXYLQ22
RXYLQ24
RXYLQ26
RXYLQ28
RXYLQ30
RXYLQ32
RXYLQ34
RXYLQ36
RXYLQ38
RXYLQ40
RXYLQ42
For all models:
Phase and frequency: 3N~ 50 Hz
Voltage: 380~415 V
Transmission line section: 0.75~1.25 mm
transmission wiring exceeds these limits, it may result in communication error.
For non-standard combinations
Calculate the recommended fuse capacity.
Formula
Calculate, by adding the minimum circuit amps of each used unit
(according to the table above), multiply the result by 1.1 and
select the next higher recommended fuse capacity.
Example
Combining the RXYLQ18 by using the RXMLQ8 and the RXYLQ10.
Minimum circuit ampacity of the RXMLQ8=16.1 A
Minimum circuit ampacity of the RXYLQ10=22.0 A
Accordingly, the minimum circuit ampacity of the RXYLQ18=16.1 A
+22.0 A=38.1 A
Multiply the above result by 1.1: (38.1 A×1.1)= 41,91 A, so the
recommended fuse capacity would be 45 A.
19
Electrical installation
|
Minimum circuit
Recommended
ampacity
16.1 A
22.0 A
24.0 A
27.0 A
32.2 A
38.1 A
44.0 A
46.0 A
48.0 A
51.0 A
54.0 A
66.0 A
68.0 A
70.0 A
72.0 A
75.0 A
78.0 A
81.0 A
2
, maximum length is 1000 m. If the total
Installer and user reference guide
fuses
20 A
25 A
32 A
32 A
40 A
45 A
50 A
60 A
60 A
60 A
60 A
80 A
80 A
80 A
80 A
90 A
90 A
90 A
107