Troubleshooting
Main code
Master
Installer and user reference guide
144
Sub code
Slave 1
Slave 2
Cause
Discharge temperature sensor
malfunction (R21T): open
circuit - A1P (X29A)
Discharge temperature sensor
malfunction (R21T): short
circuit - A1P (X29A)
Discharge temperature sensor
malfunction (R22T): open
circuit - A1P (X29A)
Discharge temperature sensor
malfunction (R22T): short
circuit - A1P (X29A)
Compressor casing
temperature sensor
malfunction (R8T): open
circuit - A1P (X29A)
Compressor casing
temperature sensor
malfunction (R8T): short
circuit - A1P (X29A)
Suction temperature sensor
malfunction (R3T) - A1P
(X30A)
De-icing temperature sensor
malfunction (R7T) - A1P
(X30A)
Liquid temperature sensor
(after subcool HE) malfunction
(R5T) - A1P (X30A)
Liquid temperature sensor
(coil) malfunction (R4T) - A1P
(X30A)
Gas temperature sensor (after
subcool HE) malfunction (R6T)
- A1P (X30A)
High pressure sensor
malfunction (S1NPH): open
circuit - A1P (X32A)
High pressure sensor
malfunction (S1NPH): short
circuit - A1P (X32A)
Solution
Check connection on PCB or
actuator.
Check connection on PCB or
actuator.
Check connection on PCB or
actuator.
Check connection on PCB or
actuator.
Check connection on PCB or
actuator.
Check connection on PCB or
actuator.
Check connection on PCB or
actuator.
Check connection on PCB or
actuator
Check connection on PCB or
actuator.
Check connection on PCB or
actuator.
Check connection on PCB or
actuator.
Check connection on PCB or
actuator.
Check connection on PCB or
actuator.
RXMLQ8 + RXYLQ10~14T7Y1B*
VRV IV system air conditioner
4P543427-1A – 2020.10

Hide quick links:

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the VRV IV and is the answer not in the manual?

Questions and answers

MUHAMMAD SHAMSUDDEEN
March 21, 2025

Hi, kindly assist me with resolving the problem of the VRV IV series. It pops up from the remote control, and after checking the master and the slaves, both cannot identify their ID number. though the last error was e2. Someone messed up with the wiring, perhaps the communication cable. If we can see what cable goes to the first unit from the master, we have 16 units attached.

1 comments:
Mr. Anderson
March 21, 2025

The troubleshooting steps for a Daikin VRV IV series system with an E2 error and communication issues between the master and slave units are:

1. Check Q1/Q2 Wiring: Inspect the wiring connections between the master and slave units at the Q1/Q2 terminals. Faulty or incorrect wiring can cause communication failures.

2. Verify Indoor-Outdoor Wiring: Ensure that the wiring between the indoor and outdoor units is correctly connected at the Q1/Q2 and F1/F2 terminals. Incorrect connections can lead to system malfunctions.

3. Check System Test Run: If the system test run was not executed or ended abnormally, perform the test run again to identify potential issues.

4. Confirm Indoor Unit Configuration: Ensure that the number of indoor units connected to the F1/F2 line does not exceed the system's capacity. Too many units can cause communication failures.

5. Inspect System Compatibility: Verify that the indoor units connected are compatible with the system (e.g., R410A, R407C, Hydrobox). Mixing incompatible units may cause communication issues.

6. Examine Outdoor Unit Wiring: Ensure that the interconnecting wiring between outdoor units in the same piping system is connected to the Q1/Q2 (Out Multi) terminals. Incorrect wiring to the F1/F2 terminals can cause system malfunctions.

Following these steps should help diagnose and resolve communication issues in the VRV IV system.

This answer is automatically generated

Subscribe to Our Youtube Channel

Table of Contents

Save PDF