Daikin VRV IV Installer And User Reference Manual page 141

System air conditioner
Hide thumbs Also See for VRV IV:
Table of Contents

Advertisement

RXMLQ8 + RXYLQ10~14T7Y1B*
VRV IV system air conditioner
4P543427-1A – 2020.10
DANGER: RISK OF EXPLOSION
Pump down – Refrigerant leakage. If you want to pump down the system, and there
is a leak in the refrigerant circuit:
Do NOT use the unit's automatic pump down function, with which you can collect
all refrigerant from the system into the outdoor unit. Possible consequence: Self-
combustion and explosion of the compressor because of air going into the
operating compressor.
Use a separate recovery system so that the unit's compressor does NOT have to
operate.
NOTICE
Make sure to NOT recover any oil while recovering refrigerant. Example: By using an
oil separator.
23
Maintenance and service
|
Installer and user reference guide
141

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents