Item
Return temperature
Set the return temperatures for "Heat",
Return time
"Cool", and "Auto" and the return time.
Use
or time.
The setting ranges are as follows.
y Return temperature for heating:
y Return temperature for cooling (dry):
y Return temperature for auto:
y Return time (shared):
Auto return
The auto return function is enabled for
the selected indoor unit if you put a check
mark here.
The following items are settings common to all indoor units.
y Eco dirc. only
Select the conditions for return.
y Always return
When you select "Eco dirc. only", the
return to the set temperature only occurs
automatically if it saves energy.
y Allow auto C/H
When you select "Allow auto C/H",
y Fan switching
temperature auto return control also
occurs in the automatic mode.
When you select "Fan switching", when
the running mode of the indoor units is
switched to "Auto Cool/Heat" the mode
switches from automatic mode to fan
mode, irrespective of the return time.
5
Touch [Register].
The "Setting" dialogue closes.
z
To cancel the settings, touch [Cancel].
z
Automatically return to set temperatures [Set temp. auto return]
Explanation
to set the temperature
16 to 30 °C*
(1 °C intervals)
1
*1 The upper limit temperature for
some models is 26 °C.
18 to 30 °C (1 °C intervals)
17 to 27 °C (1 °C intervals)
0 to 240 minutes (5 minute intervals)
5
6
Set other indoor units.
Repeat steps 3 to 5.
z
7
Touch [Reg.].
To cancel the settings, touch [Cancel].
z
78
7