Panasonic CZ-256ESMC3 Operating Instructions Manual page 166

Intelligent controller
Hide thumbs Also See for CZ-256ESMC3:
Table of Contents

Advertisement

The "Event control" screen
A:
Set the event name with
change the event names. (→ "Changing an
event name" (P.167))
B:
The settings for the selected event name
are enabled if you put a check mark here.
C:
Select the conditions.
AND
The event at the output point is
executed when the conditions set
for the input point are all met.
OR
The event at the output point is
executed when at least one of the
conditions set for the input point
are met.
D:
Set the output point event execution timing
(time).
The "OutptDlayTme" setting dialogue is
displayed when you touch this. Setting
values are "0Sec.", "1Sec.", "3Sec.",
"5Sec.", "10Sec.", "30Sec.", "1Min.",
"3Min.", "5Min.", and "10Min.".
E:
The list of input points that are set is
displayed.
Input point
This displays the input targets for which conditions are set.
Type
The input target type is displayed.
Status
The input target status is displayed.
Symbol
A symbol is displayed when temperature is set as a condition for indoor units. The symbols displayed are as follows:
F:
The list of output points that are set is displayed.
Output point
This displays the output targets for which conditions are set.
Type
The output target type is displayed.
Output
The output target status is displayed.
G:
When an input point border or output point border is selected and you touch it, the dialogue for setting each of them is displayed.
. You can
A
E
↑: When the temperature is set to "min."
↓: When the temperature is set to "max."
Linked control of air conditioning units
B
166
C
D
F
G

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents