Panasonic CZ-256ESMC3 Operating Instructions Manual page 220

Intelligent controller
Hide thumbs Also See for CZ-256ESMC3:
Table of Contents

Advertisement

Calculations for load distribution
Load distribution is calculated according to the following flow.
Outdoor units
Calculation
Electricity
Gas
Gas for generation
Standby power
Electricity with energy saving
considered
Gas with energy saving considered
Night time electricity for ice thermal
storage
High pressure saturate temperature
Adaptor
Calculation
Super heat
Sub cool
Operational performance rate
Fans speed conversion value
Work performance
Electricity
capacity
Gas
Intelligent Controller
Setting
Heater capacity
Value added for fan current
Calculation
PIA = f (PS, T2, PINp, PINg)
Electricity
PIA' = f (PIA, TS, PS, W, H, R, B)
Gas
PGA = f (GIN, TG, PG)
Calculation
Electricity distribution rate
Gas distribution ratio
Note
y "f" indicates a function calculation.
For example, "Operational performance rate D=f (SH, SC)" means that the operational performance rate is calculated using "Super heat SH"
and "Sub cool SC".
T2
TG
PG
TS
T3
TG3
TCnight
HPS
SH = f (E3, E1)
SC = f (HPS, E1)
D = f (SH, SC)
FI = f (WS)
PINp = f (D, FI, PS)
PINg = f (0)
GIN = f (D, FI, PS)
Calculation
H
B
RPI = f (PIA')
Calculation
RGI = f (PGA)
220
Methodology for calculating distributions
Indoor units
Calculation
Operating times according to fan
speed
ON hours for heater
Indoor performance
Energy recovery inlet and outlet
temperatures
Actual fan speed
Flow of measured values and settings
Flow of calculated values
Count
Number of electricity pulses
Number of gas pulses
Elements related to ice thermal
storage
Setting
Electricity
Volume of pulse units
Gas
PI = f (RPI, Pc, @e, ICE, Pice)
Amount of electricity used
Amount of gas used
GI = f (RGI, Gc, @g)
R
W
PS
E1, E2,
E3
WS
Pc
Gc
ICE = f (TCnight, RPI)
Pice = f (Pc, @e)
@e
@g

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents