Table B.4 Service Menu Alarm Settings by Line ID (continued)
Line
Parameter
ID
Name
Event Enabled
Event: ECO HI TEMP
OVERRIDE
Event Delay Time
(sec)
S298
Event Enabled
Event: TEMP CTRL
SENSOR FAIL
Event Delay Time
(sec)
S2A2
Event Enabled
Event: HIGH DEW
POINT
Event Delay Time
(sec)
S2A3
Event Enabled
Event: LOW DEW
POINT
Event Delay Time
(sec)
S2A4
Event Enabled
Event: HI DEW
POINT SENSOR A
Event Delay Time
(sec)
S2A5
Event Enabled
Event: LOW DEW
POINT SENSOR A
Event Delay Time
(sec)
S2A6
Event Enabled
Event Delay Time
(sec)
S2A7
Event Enabled
Event Delay Time
S2A8
160
Default
Range
Setting
Disabled Enabled
Enabled
MESSAGE WARNING
WARNING
ALARM
10 - 9999 sec
10 sec
Disabled Enabled
Enabled
MESSAGE WARNING
ALARM
ALARM
10 - 9999 sec
30 sec
Disabled Enabled
Enabled
MESSAGE WARNING
WARNING
ALARM
10 - 9999 sec
30 sec
Disabled Enabled
Enabled
MESSAGE WARNING
WARNING
ALARM
10 - 9999 sec
30 sec
Disabled Enabled
Enabled
MESSAGE WARNING
WARNING
ALARM
10 - 9999 sec
30 sec
Disabled Enabled
Enabled
MESSAGE WARNING
WARNING
ALARM
10 - 9999 sec
30 sec
Disabled Enabled
Enabled
MESSAGE WARNING
WARNING
ALARM
10 - 9999 sec
30 sec
Disabled Enabled
Enabled
MESSAGE WARNING
WARNING
ALARM
10 - 9999 sec
10 sec
Description
Temperature Control Sensor Fail
High Dew Point
Low Dew Point
High Dew Point Sensor A
Low Dew Point Sensor A
High Remote Sensor
Low Remote Sensor
Power A Failure