Table B.4 Service Menu Alarm Settings by Line ID (continued)
Line
Parameter
ID
Name
Event: COMP 2
SHORT CYCLE
Event Delay Time
(sec)
S290
Event Enabled
Event: EMERGENCY
POWER
Event Delay Time
(sec)
S291
Event Enabled
Event: CONDENSER
1 FAILURE
Event Delay Time
(sec)
S292
Event Enabled
Event: CONDENSER
2 FAILURE
Event Delay Time
(sec)
S293
Event Enabled
Event: EC FAN
FAULT
Event Delay Time
(sec)
S294
Event Enabled
Event: HI SUPPLY
TEMPERATURE
Event Delay Time
(sec)
S295
Event Enabled
Event: LO SUPPLY
TEMPERATURE
Event Delay Time
(sec)
S296
Event Enabled
Event: REDUCED
ECO AIRFLOW
Event Delay Time
S297
(sec)
Default
Range
Setting
MESSAGE WARNING
WARNING
ALARM
10 - 9999 sec
10 sec
Disabled Enabled
Enabled
MESSAGE WARNING
WARNING
ALARM
10 - 9999 sec
10 sec
Disabled Enabled
Enabled
MESSAGE WARNING
WARNING
ALARM
10 - 9999 sec
10 sec
Disabled Enabled
Enabled
MESSAGE WARNING
WARNING
ALARM
10 - 9999 sec
15 sec
Disabled Enabled
Enabled
MESSAGE WARNING
ALARM
ALARM
10 - 9999 sec
30 sec
Disabled Enabled
Enabled
MESSAGE WARNING
WARNING
ALARM
10 - 9999 sec
30 sec
Disabled Enabled
Enabled
MESSAGE WARNING
WARNING
ALARM
10 - 9999 sec
10 sec
Disabled Enabled
Enabled
MESSAGE WARNING
WARNING
ALARM
10 - 9999 sec
10 sec
Description
Emergency Power
Condenser 1 Failure
Condenser 2 Failure
EC Fan Fault
High Supply Temperature
Low Supply Temperature
Reduced Eco Airflow
Eco High Temperature Override