Table B.3 User Menu Alarm Settings by Line ID (continued)
Line
Parameter
ID
Name
SP
0.000 -
Transducer
1.405
High Range
inWC
(inWC)
U240
SP
Transducer
0 - 350
High Range
Pa
(Pa)
SP
0.000 -
Transducer
1.395
Low Range
inWC
(inWC)
U241
SP
Transducer
0 - 348
Low Range
Pa
(Pa)
Table B.4 Service Menu Alarm Settings by Line ID
Line
Parameter
ID
Name
Return Sensor
Alarms Enable
S202
Return Sensor
Alarms Init Delay
High Return
Temperature Alarm
S203
Low Return
Temperature Alarm
High Return
Humidity Alarm
S204
Low Returm
Humidity Alarm
Sensor A Alarms
Enable
S205
Sensor A Alarms Init
Delay
Sensor A Low
Temperature Alarm
S206
Sensor A High
Temperature Alarm
148
Default
Range
Description
Setting
1.284
inWC
Sets the pressure range at which the High Static Pressure Out of Range alarm is activated.
320 Pa
0.000
inWC
Sets the pressure range at which the Low Static Pressure Out of Range alarm is activated.
0 Pa
Range
Disabled Enabled
10 - 9999 sec
34 - 210 °F
1.0 - 99.0 °C
34 - 210 °F
1.0 - 99.0 °C
1.0 - 99.0 %
1.0 - 99.0 %
Disabled Enabled
10 - 9999 sec
34 - 210 °F
1.0 - 99.0 °C
34 - 210 °F
1.0 - 99.0 °C
Default
Description
Setting
Enabled
Enables or disables the return temperature and humidity sensor
alarms.
90 sec
100 °F
Sets the temperature threshold for the High/Low Return
Temperature alarms.
65 °F
0.65
Sets the humidity threshold for the High/Low Return
Temperature alarms.
0.35
Disabled
Enables or disables the alarms associated with Sensor A and sets
the time delay before the alarm is annunciated.
90 sec
55 °F
Sets the temperature threshold when Sensor A High/Low
Temperature alarm will occur
90 °F
Vertiv™ | Liebert® iCOM™ Installer/User Guide