DIGITAL INPUTS

Four digital inputs are always present.
Each input can perform different functions based on the setting of the following parameters:
Settings
In.1
74
In.2
75
In.3
76
In.4
77
Reading status
S.IO
29
8
R/W
Digital input 1 function
R/W
Digital input 2 function
R/W
Digital input 3 function
R/W
Digital input 4 function
Digital I/O states
R
Table of digital input functions
0
No function (input disabled)
1
General alarm reset
2
Enable/Disable loads of L1 phase
3
Enable / Disable loads of L2 phase
4
Enable / Disable loads of L3 phase
Enable / Disable ALL loads
5
(L1,L2,L3 phases)
+32 for input in denied logic
Digital I/O states table
bit
0
State input 1
1
State input 2
2
State input 3
3
State input 4
4
State output 1
5
State output 2
6
State output 3
7
State output 4
80381_MSW_IR-12/IR-24_04-2015_ENG