Alarms Fuse_Open, Ssr_Short; And Load_Open - gefran IR-12 Configuration And Programming Manual

Multichannel power controller
Hide thumbs Also See for IR-12:
Table of Contents

Advertisement

ALARMS FUSE_OPEN, SSR_SHORT and LOAD_OPEN
Diagnostics is active to check correct functioning of the process:
- FUSE_OPEN alarm: trips at opening of internal fuse
- LOAD_OPEN alarm: trips when load is interrupted or disconnected
- SSR_SHORT alarm: trips when the solid status relay is in short circuit
NOTE1 : In PA_mode, the diagnostic Alarms Load-Open and Fuse_open are detected for SCR power firing higher than 40%.
NOTE2: In PA_mode, the diagnostic Alarm SSR-SHORT is detected when SCR power firing is P=0% or when its channel
is disabled.
The summary status of the alarms is shown in S.Alarm and the details for each output are shown in S.Out.Lp.o
(with p = phase from 1 to 3, o = output from 1 to 8).
Reading status
S.Out.L1.1
80
S.Out.L1.2
81
S.Out.L1.3
82
S.Out.L1.4
83
S.Out.L1.5
84
S.Out.L1.6
85
S.Out.L1.7
86
S.Out.L1.8
87
S.Out.L2.1
88
S.Out.L2.2
89
S.Out.L2.3
90
S.Out.L2.4
91
S.Out.L2.5
92
S.Out.L2.6
93
S.Out.L2.7
94
S.Out.L2.8
95
S.Out.L3.1
96
S.Out.L3.2
97
S.Out.L3.3
98
S.Out.L3.4
99
S.Out.L3.5
100
S.Out.L3.6
101
S.Out.L3.7
102
S.Out.L3.8
103
10
Status of output 1 phase L1
R
R
Status of output 2 phase L1
R
Status of output 3 phase L1
Status of output 4 phase L1
R
R
Status of output 5 phase L1
R
Status of output 6 phase L1
R
Status of output 7 phase L1
R
Status of output 8 phase L1
R
Status of output 1 phase L2
R
Status of output 2 phase L2
Status of output 3 phase L2
R
R
Status of output 4 phase L2
R
Status of output 5 phase L2
R
Status of output 6 phase L2
R
Status of output 7 phase L2
R
Status of output 8 phase L2
R
Status of output 1 phase L3
R
Status of output 2 phase L3
R
Status of output 3 phase L3
R
Status of output 4 phase L3
R
Status of output 5 phase L3
R
Status of output 6 phase L3
Status of output 7 phase L3
R
R
Status of output 8 phase L3
Table of output states
bit
0
= 0: output OFF; = 1: output ON
= 0: proper compensation;
1
= 1: output saturated (compensation is not correct)
2
3
4
Output state: power channel interrupted (fuse or solid state relay)
5
Output state: load interrupted or disconnected
6
Output state: solid state relay in short circuit
80381_MSW_IR-12/IR-24_04-2015_ENG