to return to the previous.
CAUTION: Please change inner controller parameters (rated generator voltage,
generator frequency etc.) only in standby mode, otherwise in can lead to shutdown
or other abnormal condition.

8. COMMISSIONING

It is recommended that the following checks are made before starting the system:
1. Check that all the connections are correct and wire sizes are suitable.
2. Ensure all parameters are configured correctly and oil pressure light is on.
3. Ensure the controller DC power supply is fused and correctly connected to the
positive and negative of starter battery.
4. Take proper measures to prevent the engine from starting (e. g. unplug fuel valve
wire). After checking that there are no faults, connect the starter battery, change
start key position from OFF to ON, and the controller will carry out the procedure.
5. Then change start key position to START to start cranking. After the engine is
fired, remove start key; voltage, frequency and power windows will show true
collected values.
6. For further information please contact Smartgen services.
HGM501 Genset Controller
HGM501Genset Controller
Version V1.0
2012-07-10
Page 13 of 15