4.2. START/STOP OPERATION

4.2.1

STARTING PROCEDURE

In stop mode turn the starter key from OFF to ON position to power on the
controller, then change the starter key position to START to begin cranking; after
the engine fires, release the starter key, and voltage, power and frequency
windows will show the real measured values. Press
switchover between indicators 1#-6# and multifunctional window will show
corresponding settings. Press
LED indicators state:
1#
Frequency (Hz)
2#
Current (A)
3#
Battery voltage (V)
4#
Run time (H)
5#
Engine temp.(℃)
6#
Generator temp.(℃)
7#
Auto protection
8#
Run on indicator
9#
Crank indicator
10# Engine oil warning
NOTE: Before starting the engine please make sure that all the parameter
settings are correct.
NOTE"Engine oil warning"indicator operates according to the oil pressure
switch. Before the start of the gen-set, the light must be on; if it is not, it means that
oil pressure switch or its return circuit is faulty; in this case please do not proceed
before clearing up the problem.

4.2.2 STOPPING PROCEDURE

1
Auto stop
If auto protection condition occurs, the system will be stopped
automatically;
During normal running of the gen-set, if low oil pressure signal is detected,
the set will be stopped.
2
Manual stop
Under any circumstances, if starter key is turned from ON to OFF position,
it will lead to shutdown.
HGM501 Genset Controller
HGM501Genset Controller
2. During normal operation the button switches to
the lower LED.
button to return to the frequency window.
If on, auto protection is enabled; if not, it is
disabled.
Fuel relay output indicator
Start output indicator
Low oil pressure indicator
Version V1.0
or
2012-07-10
button to
Page 7 of 15