Check that the cable holder runners do not reduce these di-
stances, in this case fit the cantilever units opposite the panel
so that the air can flow vertically on the dissipator without any
obstacles.
• dissipation of device thermic power with effects on installation
room temperature.
• thermal power dissipation with limits on installation room tem-
perature.
• requires exchange with external air or an air conditioner to tran-
sfer dissipated power outside the panel.
• maximum limits of voltage and derived power of transients on
the line, for which the solid state power unit contains protective
devices (based on the model).
Table 1 EMC Emission
AC semiconductor motor controllers and conductors for non-motor
loads
Emission enclosure
compliant in firing mode single cycle and phase angle if external
filter fitted
Table 2 EMC Immunity
Generic standards, immunity standard for industrial environments EN 60947-4-3
ESD immunity
RF interference immunity
Conducted disturbance immunity
Burst immunity
Surge immunity
Magnetic fields immunity
Voltage dips, short interruptions and voltage immunity tests
Table 3 LVD Safety
Safety requirements for electrical equipment for measurement,
control and laboratory use
ATTENTION
This product has been designed for class A equipment. Use of the product in domestic environments may cause radio
interference, in which case the user may be required to employ additional mitigation methods.
EMC filters are required in PA mode (Phase Angle, i.e., SSR trigger with phase angle modulation).
The filter model and current level depend on the configuration and load used.
The power filter MUST by connected as close as possible to the GTF.
You can use a filter connected between the power line and GTF or an LC group connected between the GTF output and the load.
The CE declaration of conformity is available on request
80994B_MHW_GTF-Xtra_05-2016_ENG
• presence of dispersion current in GTF in non-conducting state
(current of a few mA due to RC Snubber circuit to protect ).
GEFRAN S.p.A. assumes no liability for any da-
mage to persons or property deriving from tam-
pering, from incorrect or improper use, or from
any use not conforming to the characteristics of
the controller and to the instructions in this User
Manual.
EN 60947-4-3
EN 60947-4-3
CISPR-11
EN 55011
EN 61000-4-2
EN 61000-4-3 /A1
EN 61000-4-6
EN 61000-4-4
EN 61000-4-4/5
Test are not required.
Immunity is demonstrated by
the successful completion of
the operating capability test
EN 61000-4-11
EN 61010-1
UL 508
Class A Group 2
4 kV contact discharge
8 kV air discharge
10 V/m amplitude modulated
80 MHz-1 GHz
10 V/m amplitude modulated
1.4 GHz-2 GHz
10 V/m amplitude modulated
0.15 MHz-80 MHz
2 kV power line
2 kV I/O signal line
Power line-line 1 kV
Power line-earth 2 kV
Signal line-earth 2 kV
Signal line-line 1 kV
100%U, 70%U, 40%U,