Electrical Connections; Power Connections - gefran GTF-Xtra Installation And Operation Manual

Power controller with overcurrent fault protection
Table of Contents

Advertisement

3.1
P
ower connections
RECOMMENDED WIRE GAUGES
Table 4
GTF CURRENT LEVEL
25A
40A
50A
60A
-
Note: Cables must be copper "Stranded Wire" or "Compact-Stranded Wire" type with maximum operating temperature 60/75°C
10
3 • ELECTRICAL CONNECTIONS
TERMINAL
CABLE WIRE
4 mm²
1/L1, 2/T1, PE
10 AWG
10 mm²
1/L1, 2/T1, PE
7 AWG
10 mm²
1/L1, 2/T1, PE
7 AWG
16 mm²
1/L1, 2/T1, PE
5 AWG
0.25 ...2.5 mm²
3/L2 (Ref. Vline)
23...14 AWG
WIRE TERMINAL
Wire terminal / Eye
2.5 Nm / Phillips screwdriver
D. 6mm
Wire terminal / Eye
2.5 Nm / Phillips screwdriver
D. 6mm
Wire terminal / Eye
2.5 Nm / Phillips screwdriver
D. 6mm
Wire terminal / Eye
2.5 Nm / Phillips screwdriver
D. 6mm
0.5 ...0.6 Nm / Screwdriver blade
wire terminal tip
80994B_MHW_GTF-Xtra_05-2016_ENG
TIGHTENING TORQUE /
TOOL
PH2 - PH3
PH2 - PH3
PH2 - PH3
PH2 - PH3
0.6 x 3.5 mm