gefran GTF-Xtra Installation And Operation Manual page 26

Power controller with overcurrent fault protection
Table of Contents

Advertisement

Function
Adapt the serial communication speed and parity of the GTF
modules to the connected supervision terminal or PLC.
The "RUN"and "STATUS" LEDs mentioned in the
procedure can vary its behavior based on on he
parameters Ld.1 e Ld.2
Procedure
1) Connect the serial cables for all modules on the network t
and to the supervision terminal.
2) Set the rotary switch on the GTF modules to be installed,
or on all modules present in case of first installation, to
*
position "0+0".
3) Check that the "RUN" and "STATUS" LEDs flash at high
frequency (10Hz).
4) The supervision terminal must transmit a series of generic
"MODBUS" read messages to the network.
5) The procedure is over when all of the "RUN" and
"STATUS"LEDs on the GTF modules flash at a normal
frequency (2Hz) (if parameter 50 Ld.1 = 16 as default).
The new speed parameter is saved permanently in each GTF;
therefore, the "AUTOBAUD SERIAL" sequence does not have
to be run at subsequent power-ups.
When the rotary switch is turned, the green
"STATUS" LED stays on steadily for about 6
seconds, after which it resumes normal operation and
saves the address.
*
Note: the address set by the rotary switches is acquired only at power-on..
26
4.1 "AUTOBAUD SERIAL 1" sequence
INSTALLATION OF
SERIAL NETWORK 1
ModBus
?
The serial network communication
YES
speed is the same as for
GTF.
NO
"AUTOBAUD"
SERIAL 1
SEQUENCE
SETTING
THE NODE
ADDRESS
OPERATIVE
FUNCTION
80994B_MHW_GTF-Xtra_05-2016_ENG
"RUN and STATUS"
LEDs flashes at 10 Hz