A# Exit Tone; A# Exit Dly Time; A# Auto Watch; A# Verify Time - Bosch D9412GV2 Program Entry Manual

Table of Contents

Advertisement

D9412GV2/D7412GV2 | Program Entry Guide | 2.0

A# Exit Tone

Default:
Yes
Selection:
Yes or No
Sounds an exit tone during exit delay at all keypads
assigned to this area.
You can turn off exit tones for individual
keypads by programming the appropriate
CC# 1 to 8 as No in CC# Exit Tone.

A# Exit Dly Time

Default:
60
Selection:
Blank (0) to 600 ( in 5 second
increments)
Exit delay time for this area when Master Exit or
Perimeter Exit arming.
Points programmed for instant alarms
generate alarms immediately, even during
exit delay. To prevent instant alarms on
points when leaving the building, the user
must cause a fault. Program P### Type
in the Point Index as 3 (Interior Follower).

A# Auto Watch

Default:
No
Selection:
Yes or No
Yes
When the area is disarmed, Watch
Mode turns on automatically.
No
When the area is disarmed, Watch
Mode must be turned on or off
manually.
Controlled points must be programmed
as P## Watch Point to generate a watch
tone.

A# Verify Time

Default:
60
Selection:
10 to 60 (in 1-second increments)
Use alarm verification with smoke detectors to reduce
the number of false fire alarms. When Verify Time is
programmed, the control panel can check smoke
detector point activations before generating alarm
signals.
Bosch Security Systems | 5/05 | F001U003636B
GV2MAIN
Do not enable the Cross Point feature
in point indexes designated for Fire
points.
Check with your authority having
jurisdiction (AHJ) to determine the
maximum verification time allowed.
Points are programmed individually to activate the
verification feature. Refer to Section 4.1 Point Index on
page 81. Any resettable Fire point can activate alarm
verification for the area to which it is assigned. Use
separate area alarm-verification relays.
To enable alarm verification on a point, program
Point Index
, Fire Point, Alarm Verify, and Resettable
as Yes.
When an Alarm Verification point senses an alarm,
the control panel automatically removes power to all
Resettable points connected to the area's Reset Sensors
relay. The sensor reset removes power to the sensors
for the amount of time programmed in Verify Time.
When power is reapplied, a 60-second confirmation
window begins. If the detector is still in alarm and
experiences another alarm during the confirmation
window, or a different Resettable Verification point in
the area senses an alarm, an alarm occurs.
Example: Verify Time is set for 20 seconds. The
alarm verification cycle starts when the detector senses
smoke or fire. No report occurs.
When the detector senses smoke or fire, the area's
sensor reset relay interrupts power to points connected
to it for the time in Verify Time.
When power restores to the points, the 60-second
confirmation window starts. If any detector, reset
during the verification time, experiences another alarm
during the confirmation window, an alarm occurs. If
there is no activity during this period, no alarm occurs
and the verification window ends. If a Verification
point senses another alarm after the window ends, a
new verification cycle begins. Refer to Table 22 on
page 35 for an example of Verify Time.
EN | 34