D9412GV2/D7412GV2 | Program Entry Guide | 2.0
2.5

Power Supervision

AC Fail Time

Default:
1
Selection:
1 to 90 (Blank and 0 are invalid)
Program the amount of time that AC power must be
off before the control panel responds to the AC failure.
The response to restoral of AC power is delayed for
the same amount of time. The control panel always
monitors AC.
AC Fail Time
When you program
is:
1, 3, 5, 7, or 9 (such as 3, 5, 11, 13, 15, 21, and so
AC Fail Time
on): The
2, 4, 6, 8, or 0 (such as 2, 4, 6, 10, 12, 20, 22, and
so on): The AC Fail Time interval is in seconds.
For the following items to be true, AC
Fail/Res Rpt must be programmed as Yes
and AC Tag Along must be programmed
as No.
AC Fail Time
When you program
is:
1, 3, or 5 (such as 3, 5, 11, 13, 15, 21, and so on):
The AC Fail Time interval is in minutes and an
AC Fail Event is sent after the loss of AC for this
amount of time.
No additional AC Fail Events are sent after 6
hours or 12 hours.
2, 4, or 6 (such as 2, 4, 6, 12, 14, 16, 22, 24, 26,
and so on): The AC Fail Time interval is in
seconds and an AC Fail Event is sent after the loss
of AC for this amount of time.
No additional AC Fail Events are sent after 6
hours or 12 hours.
7 (such as 7, 17, 27, 37, and so on): The AC Fail
Time interval is in minutes and an AC Fail Event
is sent after the loss of AC for this amount of time.
An additional AC Fail Event is sent after 6 hours if
the AC Fail condition is still present.
8 (such as 8, 18, 28, 38, and so on): The AC Fail
Time interval is in seconds and an AC Fail Event
is sent after the loss of AC for this amount of time.
An additional AC Fail Event is sent after 6 hours if
the AC Fail condition is still present.
Bosch Security Systems | 5/05 | F001U003636B
, if the second digit
interval is in minutes.
, if the second digit
GV2MAIN
9 (such as 9, 19, 29, 39, and so on): The AC Fail
Time interval is in minutes and an AC Fail Event
is sent after the loss of AC for this amount of time.
An additional AC Fail Event is sent after 12 hours
if the AC Fail condition is still present.
0 (such as 10, 20, 30, and so on): The AC Fail
Time interval is in seconds and an AC Fail Event
is sent after the loss of AC for this amount of time.
An additional AC Fail Event is sent after 12 hours
if the AC Fail condition is still present.
For the following items to be true,
must be programmed as No and
also be programmed as No.
AC Fail Time
When you program
is:
1, 3, or 5 (such as 3, 5, 11, 13, 15, 21, and so on):
The AC Fail Time interval is in minutes. No AC
Fail or AC Restoral Events are sent.
2, 4, or 6 (such as 2, 4, 6, 12, 14, 16, 22, 24, 26,
and so on): The AC Fail Time interval is in
seconds. No AC Fail or AC Restoral Events are
sent.
7 (such as 7, 17, 27, 37, and so on): The AC Fail
Time interval is in minutes. An AC Fail Event is
only sent after 6 hours if the AC Fail condition is
still present.
8 (such as 8, 18, 28, 38, and so on): The AC Fail
Time interval is in seconds. An AC Fail Event is
only sent after 6 hours if the AC Fail condition is
still present.
9 (such as 9, 19, 29, 39, and so on): The AC Fail
Time interval is in minutes. An AC Fail Event is
only sent after 12 hours if the AC Fail condition is
still present.
0 (such as 10, 20, 30, and so on): The AC Fail
Time interval is in seconds. An AC Fail Event is
only sent after 12 hours if the AC Fail condition is
still present.
EN | 25
AC Fail/Res Rpt
AC Tag Along
must
, if the second digit