9.20 Reading the configurable data log series

LogSeriesItemNo
The log series item numbers are shown in the table below. Note
that the scaling of the registers with the present values is
identical to the scaling of the logged data values except for power
values where the scaling has been changed from [1 W] to [10 W]
to fit into 16 bit.
System
Log series
Log item register
item No
0100
Pulse flow rate
0101
Pulse flow rate reverse
0102
System pulse flow rate
0200
LevelAI1
0201
FlowAI1
0202
PressureAI1
0203
CurrentAI1
0204
PercentageAI1
0205
TemperatureAI1
0206
ConductivityAI1
0207
TurbidityAI1
0208
PHmeasureAI1
Same registers as above but
0250-0258
for AI2
Same registers as above but
0300-0308
for AI3
Same registers as above but
0350-0358
for AI4
Same registers as above but
0400-0408
for AI5
0550
Digital input 1, DI1
0599
Digital input 1, DI49
0600
Digital output 1, DO1
0649
Digital output 1, DO49
Pump 1
Log series item No Log item register
1002
Current pump 1
1008
Power pump 1
1016
RPM Pump 1
Pump 2
Log series item No Log item register
2002
Current pump 2
2008
Power pump 1
2016
RPM Pump 2
36
Scale
0.1 l/s
0.01 m
0.1 l/s
0.001 bar
0.1 A
0.1 %
0.01 K
μS/cm
0.1 NTU
0.01
Bool
Scale
0.1 A
10 W
1 rpm
Scale
0.1 A
10 W
rpm