9.10 LC 241/LC 242 IO terminal mapping, modular
version
LC 241/LC 242 consists of a control cabinet with a CU 241/CU
242 control unit, an IO 242 pump module for connection of one or
two pumps, some basic IO signals and an optional IO 241 module
for extra IO signals. The mapping of the wire terminals to Modbus
registers for the two IO modules are shown in this section.
L1
CT 1A
REL 1
CT 1B
L2
COM
L3
CT 2A
N
REL 2
CT 2B
MPF1
PTC 1A
GND
PTC 1B
PTC 2A
MPF2
PTC 2B
DI 1
GND
DI 2
REL 3C
GND
REL 3
DI 3
GND
REL 3O
DI 4
GND
REL 4C
ADI
REL 4
GND
24 V
REL 4O
24 V
GND
EXT
IO 242 pump module
Terminal
Address
CT 1
00418
CT 2
00468
DI 1
00391 bit 0
DI 2
00391 bit 1
DI 3
00391 bit 2
DI 4
00391 bit 3
As DI
00391 bit 4
ADI
As AI
00351
Rel 3
00393 bit 0
Rel 4
00393 bit 1
A few IO 242 terminals are dedicated to a specific functionality and are not mapped: PTC1, PTC2, MPF1, MPF2, REL3, REL4.
28
Register name
Scale
Pump1Current
0.1 A
Pump2Current
0.1 A
UserDigitalInBlock1 bit 0
Bool
UserDigitalInBlock1 bit 1
Bool
UserDigitalInBlock1 bit 2
Bool
UserDigitalInBlock1 bit 3
Bool
UserDigitalInBlock1 bit 4
Bool
UserAnalogInput1
0.1 %
UserDigitalOutputs bit 0
Bool
UserDigitalOutputs bit 1
Bool
Description
Pump 1 current-transformer measurement
Pump 2 current-transformer measurement
User-configurable digital input 1
User-configurable digital input 2
User-configurable digital input 3
User-configurable digital input 4
User-configurable digital input 5
User-configurable analog input 1
User-configurable output relay 3
User-configurable output relay 4