11.6 Alarms and warnings

These registers reflect the actual alarm and warning conditions of
the system or the pump. Alarms and warnings which have
acknowledgement type "Auto-ack" are cleared automatically
when normal conditions are restored. Alarms and warnings which
have acknowledgement type "Manual-ack" require a
Control.ResetAlarm command to be cleared.
Warnings use the same bit interpretation as alarms,
they are just placed in other registers.
Description
System alarms 1 (register 00210) and System warnings 1 (register 00213)
High-level alarm
Dry-running alarm
Float-switch sequence inconsistency
Communication fault, I/O module
CIM fault (Communication Interface Module)
System alarms 2 (register 00211) and System warnings 2 (register 00214)
Signal fault, user-defined sensor 1
System alarms 3 (register 00212) and System warnings 3 (register 00215)
Water-on-floor alarm
User-event 1 alarm
User-event 2 alarm
Limit exceeded sensor 1 alarm
Limit exceeded sensor 2 alarm
External fault signal
Intrusion, door opened
Memory access error
Internal communication error
Setup conflict
System alarms 5 (register 00272) and System warnings 5 (register 00273)
Performance requirement cannot be met
External warning signal
Missing cable detected, cable theft
Real-time clock out of order
Pump alarms 1 (registers 00423, pump 1 and 00473, pump 2).
Pump warnings 1 (registers 00426, pump 1 and 00476, pump 2).
Motor-temperature alarm, PTC1
Motor-phase sequence reversal
Motor overload (maximum current)
Motor missing phase
Data item
SystemAlarms/Warnings1.1
SystemAlarms/Warnings1.3
SystemAlarms/Warnings1.5
SystemAlarms/Warnings1.11
SystemAlarms/Warnings1.12
SystemAlarms/Warnings2.13
SystemAlarms/Warnings3.1
SystemAlarms/Warnings3.3
SystemAlarms/Warnings3.4
SystemAlarms/Warnings3.8
SystemAlarms/Warnings3.9
SystemAlarms/Warnings3.10
SystemAlarms/Warnings3.12
SystemAlarms/Warnings3.13
SystemAlarms/Warnings3.14
SystemAlarms/Warnings3.15
SystemAlarms/Warnings5.0
SystemAlarms/Warnings5.1
SystemAlarms/Warnings5.2
SystemAlarms/Warnings5.3
PumpAlarms/warnings1.0
PumpAlarms/Warnings1.9
PumpAlarms/Warnings1.10
PumpAlarms/Warnings1.13
Code
Event source
191
System
57
System
205
System
226
Pump module
159
Add-on CIM module
165
User-defined sensor, analog input 1
229
System
249
System
250
System
System
94
Only supported by LC 2X2.
System
95
Only supported by LC 2X2.
System
3
Only supported by LC 2X2.
117
System
84
System
76
System
25
System
System
17
Only supported by LC 2X2.
System
46
Only supported by LC 2X2.
System
130
Only supported by LC 2X2.
System
157
Only supported by LC 2X2.
69
Pump No [1; 2]
9
Pump No [1; 2]
48
Pump No [1; 2]
2
Pump No [1; 2]
43