Diagnostics, 0X08; Diagnostics Register Interpretation - Grundfos CIM 200 Functional Profile And User Manual

Modbus for level control 2x1/2x2
Hide thumbs Also See for CIM 200:
Table of Contents

Advertisement

12.6 Diagnostics, 0x08

Diagnostics is only supported by Modbus RTU.
This function provides a test for checking the communication
system between the master and the Grundfos slave. It contains a
single-byte subcode to identify the test to be performed.
The following subcodes are supported:
Subcode Name
Return query data.
Data in this request are to be echoed in the
0x00
response. The response must be identical to the
request, so this function is often used to verify
Modbus communication.
Restart communications.
0x01
All communication counters are cleared, and the
device is restarted.
Return diagnostics register.
0x02
Returns the 16-bit diagnostics register. See section
12.7 Diagnostics register
Force listen only.
Forces the device into listen-only mode. This
effectively mutes the device, making it unable to
0x04
communicate on the network. To bring the device
back to normal mode, a "Restart communications"
command, code 0x08, subcode 0x01, must be
issued.
Clear counters and diagnostics register.
0x0A
Clears all counters and the diagnostics register.
These are also cleared on power-up and restart.
Return bus message count.
0x0B
Returns the number of messages detected by the
slave.
Return bus CRC error count.
0x0C
Returns the number of CRC errors in the slave.
Return bus exception count.
0x0D
Returns the number of Modbus exception responses
that the slave has transmitted.
Return slave message count.
0x0E
Returns the number of messages that the slave has
processed.
Return slave no response count.
0x0F
Returns the number of messages for which the
slave has sent no response.
interpretation.

12.7 Diagnostics register interpretation

The diagnostics register is interpreted as follows:
Bit
Description
0
Communication failure, with the Grundfos product.
1
RESERVED
2
Grundfos product is not supported.
Modbus address offset is different from default value, i.e.
3
it differs from 0.
4
Using software-defined Modbus transmission speed.
5
RESERVED
6
RESERVED
7
RESERVED
8
RESERVED
9
RESERVED
10
RESERVED
11
RESERVED
12
RESERVED
13
RESERVED
14
RESERVED
15
RESERVED
A bit value of 1 means that the statement in the description is
true, unless otherwise specified. The diagnostics register is read
using function code 0x08 and subcode 0x02.
47