Grundfos CIM 200 Functional Profile And User Manual page 22

Modbus for level control 2x1/2x2
Hide thumbs Also See for CIM 200:
Table of Contents

Advertisement

Address
Register name
PumpsAlarm
Bit 0: Pump1Alarm
00209
PumpsAlarm
Bit 1: Pump2Alarm
00210
SystemAlarms1
00211
SystemAlarms2
00212
SystemAlarms3
00213
SystemWarnings1
00214
SystemWarnings2
00215
SystemWarnings3
00216
EventLogLatestID
00217
NumberOfFloatSwitches
FloatSwitchesStatus
Bit 0: FloatSwitch1Status
FloatSwitchesStatus
Bit 1: FloatSwitch2Status
FloatSwitchesStatus
00218
Bit 2: FloatSwitch3Status
FloatSwitchesStatus
Bit 3: FloatSwitch4Status
FloatSwitchesStatus
Bit 4: FloatSwitch5Status
00219
FloatSwitch1Function
00220
FloatSwitch2Function
00221
FloatSwitch3Function
22
Scale
Description
Alarm state of pump 1.
0: No alarm
1: Alarm.
Bool
Alarm state of pump 2.
0: No alarm
1: Alarm.
System alarm events, item 1.
Bits
Bit-interpreted. See section
System alarm events, item 2.
Bits
Bit-interpreted. See section
System alarm events, item 3.
Bits
Bit-interpreted. See section
System warning events, item 1.
Bits
Bit-interpreted. See section
System warning events, item 2.
Bits
Bit-interpreted. See section
System warning events, item 3.
Bits
Bit-interpreted. See section
Unscaled
ID code of the latest event log.
enum
Number of installed float switches in the system, 0-5.
On and off state of float switch 1, if installed.
0: Off
1: On.
On and off state of float switch 2, if installed.
0: Off
1: On.
On and off state of float switch 3, if installed.
0: Off
Bool
1: On.
On and off state of float switch 4, if installed.
0: Off
1: On.
On and off state of float switch 5, if installed.
0: Off
1: On.
Function of the float switch.
0: RESERVED
1: Dry running
2: -
enum
3: Stop of all pumps
11: Start or stop
14: Start of first pump
15: Start of second pump
23: High level.
Function of the float switch.
0: RESERVED
1: Dry running
2: -
enum
3: Stop of all pumps
11: Start or stop
14: Start of first pump
15: Start of second pump
23: High level.
Function of the float switch.
0: RESERVED
1: Dry running
2: -
enum
3: Stop of all pumps
11: Start or stop
14: Start of first pump
15: Start of second pump
23: High level.
11.6 Alarms and
warnings.
11.6 Alarms and
warnings.
11.6 Alarms and
warnings.
11.6 Alarms and
warnings.
11.6 Alarms and
warnings.
11.6 Alarms and
warnings.