System Status Register Block - Grundfos CIM 200 Functional Profile And User Manual

Modbus for level control 2x1/2x2
Hide thumbs Also See for CIM 200:
Table of Contents

Advertisement

9.5 System status register block

Registers in this block can be read by means of function codes
0x03 and/or 0x04. It is not possible to write to these registers.
Unless otherwise stated, the data type used for counters and
scaled values is always an unsigned integer.
Address
Register name
AcknowledgeRegister
Bit 0: AckResetAlarm
AcknowledgeRegister
00201
Bit 1: AckSetRtc
AcknowledgeRegister
Bit 2: AckResetEventLog
Bit 0: RESERVED
SystemStatus
Bit 1: AlarmActive
00202
SystemStatus
Bit 2: WarningActive
SystemStatus
Bit 3: ManualControl
00203
OperatingMode
PumpsPresence
Bit 0: Pump1Presence
00204
PumpsPresence
Bit 1: Pump2Presence
PumpsRunning
Bit 0: Pump1Running
00206
PumpsRunning
Bit 1: Pump2Running
PumpsMonitoringFault
Bit 0: Pump1MonitoringFault
00207
PumpsMonitoringFault
Bit 1: Pump2MonitoringFault
PumpsWarning
Bit 0: Pump1Warning
00208
PumpsWarning
Bit 1: Pump2Warning
Scale
Description
Indicates if a ResetAlarm control bit was acknowledged by the device.
This bit is only active if AutoAckControlBits (register 00005, bit 0) is set
to "0".
0: Not acknowledged
1: Acknowledged.
Indicates if a SetRtc (real-time clock) control bit was acknowledged by
the device. This bit is only active if AutoAckControlBits (register 00005,
Bool
bit 0) is set to "0".
0: Not acknowledged
1: Acknowledged.
Indicates if a ResetEventLog control bit was acknowledged by the
device. This bit is only active if AutoAckControlBits (register 00005, bit
0) is set to "0".
0: Not acknowledged
1: Acknowledged.
-
-
Alarm condition.
0: No active alarms
1: One or more active alarms.
Warning condition.
Bool
0: No active warnings
1: One or more active warnings.
Manual control condition.
0: No manual control
1: Manual control.
Register for reading the actual operating mode of the system.
0: Standby, stopped from level control
1: Startup delay
2: Pumping
3: Stop delay
4: Pumping max.
enum
5: Stopped
8: Pump anti-seizing
9: Manual control, all enabled pumps in manual control mode
12: Level-sensor fault
13: All enabled pumps in alarm
14: All pumps out of operation
Presence of pump 1.
0: Not present
1: Present.
Bool
Presence of pump 2.
0: Not present
1: Present.
Running state of pump 1.
0: Not running
1: Running.
Bool
Running state of pump 2.
0: Not running
1: Running.
Fault state of pump 1 monitoring devices, always 0 for LC controllers.
0: No fault
1: Fault in auxiliary equipment or sensors.
Bool
Fault state of pump 2 monitoring devices, always 0 for LC controllers.
0: No fault
1: Fault in auxiliary equipment or sensors.
Warning state of pump 1.
0: No warning
1: Warning.
Bool
Warning state of pump 2.
0: No warning
1: Warning.
21