Chapter 5 – Programming

Control Locations

10.1 EXT 1 STRT /
STP / DIR
10.2 EXT 2 STRT /
STP / DIR
11.2 EXT 1/EXT 2
REF SEL
5-6
The ACS 600 drive can receive control information from multiple sources,
including discrete I/O, analogue I/O, keypad, and communication modules.
The source for the control information must be programmed through the panel
to the drive.
Configuration is done for Control Location variables. These variables are
described for the Modbus Plus interface in the following paragraphs.
Defines the source for Start and Stop Control, as well as for Direction control,
when the drive uses External Reference 1.
NOT SEL
The external control source is not selected.
DI1, ..., DI6,5
Start, Stop, and Direction information is received using digital inputs. For
details see the ACS 600 Programming Manual.
KEYPAD
Start, Stop, and Direction information is received from the control panel. For
details see the ACS 600 Programming Manual.
COMM MODULE
The Start, Stop, and Direction control is received from the communication
option module. This data is received using data set number one, the Control
Word.
The Control Word can be received either by using Global Data, or by doing a
register write to address 40001.
Defines the source for Start and Stop Control, as well as for Direction control,
when the drive uses External Reference 2. The choices are the same as Param-
eter 10.1 EXT 1 STRT/STP/DIR.
Defines which reference (External Reference 1 or External Reference 2) is
being used.
DI1, ... , DI6
The selection is done with a digital input signal.
EXT 1
External Reference 1 is in use.
EXT 2
External Reference 2 is in use.
COMM MODULE
The selection is done by bit 5 of the Control Word.
Installation and Start-up Guide for NMBP-01