ABB NMBP-01 Installation And Startup Manual page 50

Modbus plus adapter module for acs 600
Table of Contents

Advertisement

Appendix B – Parameter Scaling
ANALOGUE OUTPUT SELECTIONS for data sets 5 and 6
Analogue Output
PROCESS SPEED
SPEED
FREQUENCY
CURRENT
TORQUE
POWER
DC BUS VOLTAGE V
OUTPUT VOLTAGE
EXTERNAL REF 2
APPL BLOCK OUTPUT
ACTUAL VALUE 1
ACTUAL VALUE 2
CONTROL DEVIATION
B-2
Short name
Description
P SPEED
Process speed
SPEED
Motor speed
FREQ
ACS 600 output frequency
CURRENT
Motor current
TORQUE
Motor torque
POWER
Motor power
DC BUS V
DC bus voltage of ACS 600
OUT VOLT
Calculated motor voltage
EXT REF2
External reference 2
APPL OUT
Output of the PID controller (if the
PID Macro is selected), External
reference 2 (External control active),
or Keypad reference 2 (Local control
active)
ACT VAL1
PID controller Actual value 1
Available only if the PID Macro is
selected
ACT VAL2
PID controller Actual value 2
Available only if the PID Macro is
selected
CONT DEV
The difference between the PID
controller reference and the PID
controller actual signal. Available
only if the PID Macro is selected
Scaling
-20000
-100 %
20000
100 %
of the value defined with
Parameter 20.1 or 20.2 (DTC Control
Mode) or Parameter 20.7 or 20.8
(SCALAR Control Mode)
-100
-1 Hz
100
1 Hz
0
0 %
10000
100 %
of motor nominal current
-10000
-100 %
10000
100 %
of motor nominal torque
0
0 %
10000
100 %
of motor nominal power
0
0 %
10000
100 %
of nominal DC bus voltage
(560 V d.c. for 380 to 415 V a.c. units;
675 V d.c. for 380 to 500 V a.c. units)
0
0 %
10000
100 %
of motor nominal voltage
0
0 %
10000
100 %
of motor max. speed / nominal torque /
max. process reference (selected with
Parameter 11.6)
0
0 %
10000
100 %
0
-100 %
10000
100 %
Installation and Start-up Guide for NMBP-01