ABB NMBP-01 Installation And Startup Manual page 21

Modbus plus adapter module for acs 600
Table of Contents

Advertisement

Modbus Plus
Modbus Plus Cable
Installation and Start-up Guide for NMBP-01
The NMBP-01 option module has the standard 9-pin D-shell Modbus Plus
connector on top of the front plate.
The following chapters are used by permission of Modicon. These chapters
are taken from Modicon publication " Modbus Plus Network Planning and
Installation Guide" (GM-MBPL-001 Rev. D).
The cable type specified for network use is:
Manufacturer:
Telephone:
Cable Type:
Description: Twisted pair, shielded, with insulating outer jacket NEC/UL
CM (communications) for use in industrial environments
This cable is available from Modicon as the following part numbers:
97-9841-100
97-9841-500
97-9841-01K
For ordering information, contact Modicon Customer Service at the following
telephone numbers. Ask for Customer Service Order Entry.
North America:
International:
Your cable will run directly between the network device locations. Each cable
segment must be a continuous run between the device connectors at two loca-
tions. The use of splices, taps, splitters, or any other configurations such as
'star' or 'tree' configurations, is not allowed. The only allowed media compo-
nents are the network cable and network device connectors.
You will typically plan your cable runs according to the vertical rises and hor-
izontal distances between sites. When you order cable, you will be ordering it
by reels of fixed length. Order reels of sufficient length to allow continuous
runs between the network devices. Provide excess length at each site for ser-
vice loops, strain reliefs, and dressing.
Chapter 4 – Electrical Installation
Belden Corporation
(317) 983-5200
9841
MBPlus 100 Foot Reel
MBPlus 500 Foot Reel
MBPlus 1000 Foot Reel
(800) 468-5342
(508) 794-0800
4-5