User Manual: WaveLinx Lite (1.5)
Device Details Occupancy Sensor Page
Setting
Default
Current Status
N/A
Hold Time
20 Minutes
Sensitivity
High
Sensor
Enabled
Occupancy Set
Occupancy Set 1 Displays the occupancy set that the sensor is assigned to. Tap
Blink to Identify
N/A
Test Mode
N/A
LED
Enabled
Description
Displays the current status of the sensor, either occupied or
unoccupied.
Note: Status reflected does not include the hold time delay. It reflects if
actual motion activity was occurring at the time the status last loaded.
Displays the Occupancy Set's programmed hold time for
informational purposes (not editable) as hold time affects an
entire occupancy set, not just one device.
Slide the switch to low sensitivity if a sensor is detecting
motion outside of the desired coverage area. Switch to High to
regain the full motion sensing range.
Slide the switch to disable the occupancy sensor for this
device. This can be helpful if a sensor is false-triggering due to
challenging placement. Examples: near air vents or doorways.
Note: It is recommended to avoid placing sensors within 3ft
(1m) of air vents.
on the right arrow icon '
' to navigate directly to the
occupancy set configuration.
Tap on the icon '
' to cause the connected fixture to flash on
and off for a 15 second period. To cancel 'blink to identify'
before the timer expires, tap '
If test mode is activated (slide switch to activate), the sensor
will be placed in test mode for 10 minutes. During test mode,
the occupancy sensor will operate with a 10 second hold time.
Note: if more than one occupancy sensor reports to the occupancy set,
use test mode at the occupancy set level to prevent other sensors in
the occupancy set from holding the lighting on.
Disabling the LED is not recommended as it is often used to
determine if the sensor is operational. If the sensor LED flash
is a major distraction, slide the switch to disabled.
' again.
www.cooperlighting.com
61
Need help?
Do you have a question about the WaveLinx Lite and is the answer not in the manual?