4.2

Operation mode setting

4.2.1

Operation mode switching and communication startup mode (Pr.79, Pr.340)

 Operation mode switching conditions
Check the following before switching the operation mode.
• The inverter is at a stop.
• Both the STF and STR signals are off.
• The Pr.79 Operation mode selection setting is correct.
(Check the setting on the operation panel of the inverter.)
 Operation mode selection at power ON and at restoration from instantaneous power failure
The operation mode at power ON and at restoration from instantaneous power failure can be selected.
Set a value other than "0" in Pr.340 Communication startup mode selection to select the network operation mode.
After started in network operation mode, parameter write from the network is enabled.
NOTE
• Change of the Pr.340 setting is valid when powering on or resetting the inverter.
• Pr.340 can be changed with the operation panel independently of the operation mode.
• Ensure that the communication setting of the inverter is completed before setting Pr.340 ≠ "0".
• For the details of Pr.79 and Pr.340, refer to the FR-E800 Instruction Manual (Function).
24
INVERTER SETTING