Mitsubishi Electric 800 Series Instruction Manual page 30

Plug-in option, profibus-dp communication function
Hide thumbs Also See for 800 Series:
Table of Contents

Advertisement

 About setting
• Operation at an error occurrence
Fault description
Communication line
Communication option
*1
When the communication returns to normal within the time period set in Pr.500, the communication option fault (E.OP1) does not occur.
• Operation after the time in Pr.500 elapses after an error occurrence
Fault description
Communication line
Communication option itself
*2
When an error occurs, the inverter outputs a command to decelerate the motor or shuts off the output, and outputs the fault,
independently of the Pr.500 setting.
*3
When the frequency command source is changed from NET to any other source, frequency commands given from an external device are
enabled.
Pr.502 setting
Operation
0
1
*1
Continued
2
6
0
Output shutoff
Output to decelerate and stop
1, 2
the motor
Operation continued at the set
6
frequency of Pr.779
Pr.502 setting
Operation
0
Output shutoff
1
Output to decelerate and stop
the motor
2
Operation continued at the set
6
frequency of Pr.779
0
Output stop status continues.
1, 2
Operation continued at the set
6
frequency of Pr.779
Indication
*1
Normal
"E. 1"
"E. 1" after stop
"CF" warning
Indication
"E.OP1"
"E.OP1" after stop
"CF" warning
*3
*2
*2
"E.1" kept
"CF" warning
*3
Fault output
*1
Not output
Provided
Provided after stop
Not output
Fault output
Provided
Provided after stop
Not output
*2
Kept provided
Not output