Mitsubishi Electric 800 Series Instruction Manual page 40

Plug-in option, profibus-dp communication function
Hide thumbs Also See for 800 Series:
Table of Contents

Advertisement

Parameter
MaxTsdr_3M
MaxTsdr_6M
MaxTsdr_12M
Redundancy
Repeater_Ctrl_Sig
24V_Pins
Freeze_Mode_supp
Sync_Mode_supp
Auto_Baud_supp
Set_Slave_Add_supp
Min_Slave_Intervall
Modular_Station
Max_Module
Max_Input_Len
Max_output_Len
Max_Data_Len
Fail_Safe
Max_Diag_Data_Len
Slave_Family
PrmText
Text(0)
Text(1)
EndPrmText
ExtUserPrmData
Bit(0) 0 0-1
Prm_Text_Ref
EndExtUserPrmData
Max_User_Prm_Data_Len
Value
50
Longest time 50 bit times at communication speed 3.0 Mbps
100
Longest time 100 bit times at communication speed 6.0 Mbps
200
Longest time 200 bit times at communication speed 12.0 Mbps
0
Redundancy not supported.
2
Installed as TTL level via RTS signal from module.
0
24 V power supply for maintenance device connection is not used.
1
Freeze mode supported.
1
Synchronous mode supported.
1
Automatic baud rate detection support
0
Slave address is not set.
1
100 μs interval between 2 polling cycles
1
Modular device specified.
1
Maximum number of modules: 1
28
Input data: Maximum 28 bytes
28
Output data: Maximum 28 bytes
56
Input and output data: Maximum 28 + 28 = 56 bytes
0
Failsafe not supported
6
1
Drives defined as function class (Main Family)
1
Text selection 1 registration
"No byte swapping"
"Byte swapping"
1 "Byte swapping"
Byte swapping selection 1 registration on text base
Bit 0 = default 0, range 0 to 1
1
Text selection 1 is used.
2
User parameter of 2 bytes secured
Description
Diagnostic data of 6 bytes secured (no external diagnosis)
If Bit 0 = 0, "No byte swapping"
If Bit 0 = 1, "Byte swapping"
PROFIBUS DEVICE DATA
*1
39
6