5.1.2 Starting the Inverter

Table 5-1 UPS system user list
Default User
admin (administrator)
operator (common user)
browser (browsing user)

5.1.2.1 Initial Startup

Step 1 After the MDU starts properly, set the language, time, network parameters, system parameters,
and battery parameters on the Settings Wizard screen.
Set system parameters with caution because the settings determine normal UPS operation.
Battery parameter settings are critical to battery maintenance, battery lifespan, and UPS
discharge time. When you set battery parameters, note the following:
Issue 04 (2020-03-03)
Output voltage level refers to the line voltage level. Set it based on site requirements.
Set Output frequency correctly; otherwise, loads may be affected and the UPS may not
work properly.
Copyright © Huawei Technologies Co., Ltd.
Preset Password
LCD
WebUI
LCD
WebUI
WebUI
5 Operations
000001
Changeme
000001
Changeme
N/A
165