UPS5000-S-1600 kVA
User Manual
Table 8-5 Bypass input electrical specifications
Item
System
Rated voltage
Rated frequency
Frequency range
Input mode
Table 8-6 Battery electrical specifications
Item
Battery voltage
Battery management
Cold start by pressing one
button
Charger output power
Charger current limit
Charging voltage
Issue 04 (2020-03-03)
Specifications
Three-phase, four-wire, and PE
380 V AC/400 V AC/415 V AC (line voltage)
50/60 Hz
50/60 Hz ± 6 Hz (adjustable with the tolerance of 0.5–6 Hz, ± 2
Hz by default)
The mains input and bypass input share a power source or use
different power sources.
Specifications
360 V DC to 600 V DC
12 V batteries, 30–50 batteries, 40 batteries by default
If there are 40 to 50 batteries, the output power is not
derated.
If there are 36 to 39 batteries, the output power is derated
to 90%.
If there are 32 to 35 batteries, the output power is derated
to 80%.
If there are 30 to 31 batteries, the output power is derated
to 70%.
2 V batteries, 180–300 batteries, 240 batteries by default
If there are 240 to 300 batteries, the output power is not
derated.
If there are 239 to 216 batteries, the output power is
derated to 90%.
If there are 215 to 192 batteries, the output power is
derated to 80%.
If there are 191 to 180 batteries, the output power is
derated to 70%.
Intelligent battery management
If a mains outage occurs, batteries can start the UPS to supply
power to loads.
Under rated conditions, the maximum charge power of a
module is 15 kW.
Maximum 32 A for a module
Equalized charging voltage: 2.3–2.4 V/cell. The default
voltage is 2.35 V/cell.
Float charging voltage: 2.23–2.3 V/cell. The default
Copyright © Huawei Technologies Co., Ltd.
8 Technical Specifications
193