Installation; Installation Preparations; Site; Installation Environment - Huawei UPS5000-S-1600 kVA User Manual

Table of Contents

Advertisement

UPS5000-S-1600 kVA
User Manual

3.1 Installation Preparations

3.1.1 Site

3.1.1.1 Installation Environment

Issue 04 (2020-03-03)
Do not install the UPS in high temperature, low temperature, or damp environments.
Install the UPS away from water sources, heat sources, and flammable or explosive
materials. Keep the UPS away from direct sunlight, dust, volatile gases, corrosive
materials, and air dense with salt particles.
Do not install the UPS in environments with conductive metal scraps in the air.
The optimal operating temperatures for valve-regulated lead-acid batteries (VRLA
batteries) are 20–30° C. Operating temperatures higher than 30° C shorten the battery
lifespan and operating temperatures lower than 20° C reduce the battery backup time.
Copyright © Huawei Technologies Co., Ltd.
3

Installation

3 Installation
50

Advertisement

Table of Contents
loading

This manual is also suitable for:

Ups5000-s-1600kva-fp

Table of Contents