Huawei UPS5000-S-1600 kVA User Manual page 42

Table of Contents

Advertisement

UPS5000-S-1600 kVA
User Manual
Port
Silk Screen Control
DO_4
NO
COM
Southbound
COM1
communications
port 1
Southbound
COM2
communications
port 2
Network port
FE
Northbound
RS485
communications
port
DB26
MDU
Battery
B_TEMP
temperature sensor
port
Figure 2-17 and Figure 2-18 are recommended wiring methods for DO ports.
Issue 04 (2020-03-03)
Module 1
In use
Controls the
entire UPS
system.
In use
In use
Controls the
entire UPS
system.
Reserved
Signal cables must be double-insulated twisted cables. If the cable length is 25–50 m, the
cross-sectional area must be 0.5–1.5 mm
RS485 cables must be shielded cables.
Copyright © Huawei Technologies Co., Ltd.
Control
Description
Module 2
alarms, battery mode, or low battery
voltage.
DO_4 is used to output alarms and
indicates battery mode by default. It can
be set to indicate critical alarms, minor
alarms, bypass mode, or low battery
voltage.
Reserved
Supported protocol: Modbus-RTU
Connects to an ambient temperature
and humidity sensor or battery
temperature sensor; two-wire system.
In use
N/A
N/A
Reserved
Supported protocol: Modbus-RTU
Connects to a northbound network
management device or a third-party
network management device over two
wires.
Provides FE, RS485, I2C, and CAN
signals.
N/A
2
.
2 Overview
34