Huawei UPS5000-S-1600 kVA User Manual page 130

Table of Contents

Advertisement

UPS5000-S-1600 kVA
User Manual
Item
bypass voltage
Minimum
bypass voltage
Bypass
frequency
range (Hz)
Battery Settings
Battery parameter settings impact battery maintenance, battery lifespan, and UPS discharge
time. When you set battery parameters, note the following:
Issue 04 (2020-03-03)
Description
bypass voltage and the rated
voltage exceeds the upper
threshold for the bypass voltage,
the system determines that the
bypass voltage is not normal and
that the bypass is unavailable.
When the difference between the
bypass voltage and the rated
voltage exceeds the upper
threshold for the bypass voltage,
the system determines that the
bypass voltage is not normal and
that the bypass is unavailable.
When the difference between the
bypass input frequency and the
rated frequency is greater than
the specified value, the system
determines that the bypass
frequency is abnormal, so the
bypass is unavailable. The
frequency range must be greater
than the ECO frequency range.
Copyright © Huawei Technologies Co., Ltd.
4 User Interface
Default Value
Value Range
the value range is +10%, +15%,
+20%, and +25%. The default
value is +15%.
When the voltage level is 400 V,
the value range is +10%, +15%,
and +20%. The default value is
+15%.
When the voltage level is 415 V,
the value range is +10% and
+15%. The default value is
+10%.
–10%, –15%,
-20%
–20%, –30%,
–40%, –50%,
–60%
± 2 Hz
± 0.5, ± 1.0, ± 2.0,
± 3.0, ± 4.0, ± 5.0,
± 6.0
122

Advertisement

Table of Contents
loading

This manual is also suitable for:

Ups5000-s-1600kva-fp

Table of Contents