Step 4 On the LCD of the system, view the system running status diagram to check that the UPS is
working in bypass mode.
----End
Offline Startup
Step 1 Open the Service Expert app on the mobile phone.
Step 2 On the home screen of the app, tap Startup to access the Set Startup screen.
Step 3 Set Site and Device Type as required, and tap Offline Activation.
Issue 04 (2020-03-03)
After you set parameters on the Settings Wizard screen, choose System Info > Settings > System
Setting. Check that System Capacity, Power module capacity, Requisite modules, and
Redundant modules match the actual values.
If dry contact signals are connected to the system, choose System Info > Settings > Dry contacts
Set and check that the connected dry contacts have been enabled and that the disconnected dry
contacts have been disabled.
If the system has connected to the remote EPO switch, you need to choose Monitoring > Param.
Settings > System Settings on the WebUI and check that EPO detection is set to Enable.
If the Inconsistent parallel param. alarm is generated, choose System Info > Settings, on the LCD
of the system and tap Parameter Sync.
The Service Expert app can be downloaded from Google Play and can run on Android.
For offline startup, enter the barcode and the verification code on the mobile phone app.
The app automatically generates a startup password for the UPS. Then enter the password
on the MDU screen to start the UPS.
If the initial startup verification passes, startup verification is not required afterwards.
After factory settings are restored, re-verification for startup is required.