Huawei UPS5000-S-1600 kVA User Manual page 186

Table of Contents

Advertisement

UPS5000-S-1600 kVA
User Manual
Automatic Shallow Discharge Test
Step 1 On the main screen of the system LCD, choose System Info > Settings > Battery Param.,
and set Sched. shallow dis. test to Enable.
Step 2 Set Sched. shallow dis. test time and Sched. shallow dis. test interval as required. After
setting is complete, the system will perform automatic shallow discharge tests based on the
settings.
----End
Manual Shallow Discharge Test
Step 1 On the home screen of the power unit LCD, choose Power Unit N Info. > Maintenance >
Battery Maint.
Step 2 Tap Start next to Shallow Dis. Test to start a shallow discharge test.
Figure 5-15 Starting the shallow discharge test
----End
Issue 04 (2020-03-03)
The UPS works in normal mode with a load ratio fluctuation less than 10%.
The UPS generates no battery overtemperature, overvoltage, or overcurrent alarm. No
generator is connected to the UPS.
The mains, batteries, charger, and discharger are normal. No overload alarm is generated.
When the battery test is complete, the test data is used as common test data. Record the data obtained
from the latest five tests.
The shallow discharge test automatically stops in any of the following cases:
The battery discharge capacity reaches the specified value (10%–50%, 20% by default).
The discharge voltage reaches the warning threshold (calculated in real time).
The load ratio fluctuation exceeds 10%.
An alarm is generated.
Copyright © Huawei Technologies Co., Ltd.
5 Operations
178