UPS5000-S-1600 kVA
User Manual
Item
voltage (V/cell)
Cell equalized
volt. (V/cell)
Dis. cur. 0.1C
EOD (V/cell)
Dis. cur. 0.3C
EOD (V/cell)
Dis. cur. 0.5C
EOD (V/cell)
Dis. cur. 1.0C
EOD (V/cell)
EOD restart
EOD restart
delay (min)
Sched. shallow
dis. test
Sched. shallow
dis. test time
Sched. shallow
dis. test interval
(d)
Shallow dis.
test dis. ratio
(%)
Issue 04 (2020-03-03)
Description
charging voltage.
Specifies the battery equalized
charging voltage.
Specifies the EOD threshold
when the discharging current is
0.1C, 0.3C, 0.5C, and 1.0C
respectively.
If the mains is not functioning
normally, the UPS will transfer
to battery mode. When batteries
reach the EOD threshold, the
bypass is disabled, and EOD
restart is Enable, the UPS will
restart as soon as the mains
resumes.
If EOD restart is disabled, clear
the alarm manually or enable the
restart function for the UPS.
If EOD restart is set to Enable,
the UPS starts working after the
time set for EOD restart delay
when the input recovers from the
power failure upon EOD.
When certain conditions are met,
the charger shuts down, and
batteries supply power to loads.
The system records the battery
discharge data as the reference
for battery capacity and lifespan.
Time for scheduled shallow
discharge test.
Interval for scheduled shallow
discharge test.
Set the proportion of the
discharge capacity to the total
discharge capacity. The value is
configurable in any mode.
Copyright © Huawei Technologies Co., Ltd.
4 User Interface
Default Value
Value Range
2.30 V/cell
2.35 V/cell
2.30 V/cell to
2.40 V/cell
1.80 V/cell
1.8–1.9
1.80 V/cell
1.8–1.9
1.75 V/cell
1.75–1.85
1.60 V/cell
1.6–1.75
Enable
Disable, Enable
10
1–1440
Disable
Disable, Enable
00:00 - 06:00
00:00 - 06:00,
06:00 - 12:00,
12:00 - 18:00,
18:00 - 24:00
60
30–90
20%
10%–50%
125