UPS5000-S-1600 kVA
User Manual
Item
Intelligent
detection
module
BCB trips if
UPS stops
power supply
Input Settings
Figure 4-23 Input settings
Item
D.G. mode
Issue 04 (2020-03-03)
Description
delay to accelerate the transfer
and prevent battery
overdischarge. Intra-rack power
module start delay (s) can be set
to a value ranging from 0.5 to
120. Inter-rack power module
start delay (s) can be set to a
value ranging from 2 to 120. The
preset value of Inter-rack power
module start delay (s) is 5.0.
The start delay of a module in a
rack varies depending on the rack
number and module number. #1
module in rack 1 does not have a
start delay.
When you set this parameter to
Enable, the intelligent
temperature detection and switch
status are displayed on the
Settings and Running screens.
Indicates whether the BCB trips
when the system stops supplying
power and the output power is
off.
Description
Set this parameter to Enable
when a D.G. connects to the
input PDC. The UPS enters the
Copyright © Huawei Technologies Co., Ltd.
4 User Interface
Default Value
Value Range
Enable
Disable, Enable
Enable
Disable, Enable
Default Value
Value Range
Disable
Disable, Enable
119