Huawei UPS5000-S-1600 kVA User Manual page 63

Table of Contents

Advertisement

UPS5000-S-1600 kVA
User Manual
Figure 3-4 Copper bar specifications (unit: mm)
Table 3-2 Recommended cross-sectional areas for power cables
Item
Mains input
Bypass input
Output
Battery input
Equipotential
ground point
Issue 04 (2020-03-03)
Mains input current (A)
Bypass input current (A)
Output current (A)
Battery nominal discharge current (A)
Battery maximum discharge current (A)
Recommended
cross-sectional area
2
(mm
) for each power
unit
Recommended cross-sectional area
2
(mm
)
The currents listed in the tables are measured at a rated voltage of 380 V.
When selecting, connecting, and routing power cables, follow local safety regulations
and rules.
When the external conditions change, for example, the cable layout or ambient
temperatures, perform verification in accordance with the IEC-60364-5-52 or the local
regulations.
Copyright © Huawei Technologies Co., Ltd.
Specifications
3046
2431
2431
3509
4203
+
3 x (2 x 240)
-
PE
240
16
3 Installation