FMS-2000C

Setting the alarms for the first time

On the home screen, tap the Isolation Mode quick link.
1.
2.
On the ROOM screen, expand Isolation Mode and choose from the following options:
Positive
Negative
Neutral
3.
Optional: If you have a secondary monitored space, tap Secondary and expand Isolation Mode to choose the isolation mode for
the secondary monitored space.
4.
To confirm the new settings, tap the Checkmark icon. The home screen appears.
5.
On the home screen, tap the Settings icon.
6.
On the SETTINGS screen, tap Analog I/O.
7.
To find the analog input you want to set up the alarm for, swipe left.
8.
Scroll down and tap the Alarm Setup arrow.
9.
Switch Alarm Enabled on.
10. Tap the High Alarm Setpoint arrow.
11. Enter the High Alarm Setpoint and tap the Checkmark to confirm your settings.
12. Tap the High Warning Limit arrow.
13. Enter the High Warning Limit and tap the Checkmark to confirm your settings.
14. Tap the Low Warning Limit arrow.
15. Enter the Low Warning Limit and tap the Checkmark to confirm your settings.
Note: If you configure your space for both positive and negative isolation mode, repeat this process and set up an alarm for the positive
and the negative isolation mode.

Changing the alarm limits

1.
On the home screen, tap the Settings icon.
2.
On the SETTINGS screen, tap Analog I/O.
3.
To find the analog input you want to set up the alarm for, swipe left.
Scroll down and tap the Alarm Setup arrow.
4.
5.
Switch Alarm Enabled on.
Tap the High Alarm Setpoint arrow.
6.
7.
Enter the High Alarm Setpoint and tap the Checkmark to confirm your settings.
Tap the High Warning Limit arrow.
8.
9.
Enter the High Warning Limit and tap the Checkmark to confirm your settings.
10. Tap the Low Warning Limit arrow.
11. Enter the Low Warning Limit and tap the Checkmark to confirm your settings.

Naming the pressure analog input

Set the name you want to appear on the home screen for a certain analog input. If you set up the FMS-2000C controller in portrait mode
you can have 16 characters. In landscape mode, you can have 12 characters.
1.
On the home screen, tap the Settings icon.
2.
On the SETTINGS screen, tap Analog I/O.
3.
To find the analog input you want to set up a name for, swipe left.
4.
Scroll down and tap the Name arrow.
5.
Enter a name for the analog input and tap the Checkmark icon to confirm it.