Johnson Controls F4-SNC Installation Manual

Johnson Controls F4-SNC Installation Manual

Hide thumbs Also See for F4-SNC:

Advertisement

Quick Links

Application
The Facility Explorer SNC Series (F4-SNC) are Ethernet-
based, supervisory controllers that connect Building
Automation System (BAS) networks to IP networks.
The SNC features onboard inputs and outputs for
direct control of equipment. This device monitors and
controls networks of field-level building automation
devices, including HVAC equipment, lighting, security,
and fire safety equipment. The SNC has FIPS 140-2 Level
1 Compliance, which is a United States government
cybersecurity standard that approves cyroptographic
modules/algorithms used for encryption.
The F4-SNC25151-0H and F4-SNC25151-04H models have a
display where you can view Alarms, Overrides, Equipment
Data, and Trends. You can command Equipment Data
points. Display settings can be viewed and edited but
Controller settings can only be viewed. You can navigate
the display using the direction arrows, back, OK, and menu
buttons.
The F4-SNC25151-0x/x models have a total of 40 I/O points
- with 25 inputs and 15 outputs. The F4-SNC16121-0x
models have a total of 28 I/O points - with 16 inputs and
Figure 1: F4-SNC25151-0x/x
F4-SNC Installation Guide
12 outputs. The first two numbers of the product code
number represent the number of inputs (SNC25151-0x/
x) and the next two numbers represent the number
of outputs (SNC25151-0x/x). The SNC offers various
integration options.
Field Bus integrations supported
• BACnet MS/TP
Ethernet integrations supported
• BACnet/IP
Physical features
The following figures display the physical features of the
SNC25151-0x/x and SNC16121-0x with display models. The
accompanying table provides a description of the physical
features and a reference to further information where
relevant.
Note: The physical features labelled with callouts
9-16 are only available on SNC models with the
display.
*241014302031A*
Part No. 24-10143-02031 Rev. A
2020-11-11
(barcode for factory use only)
F4-SNC25151-0xx, F4-SNC16121-0x

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the F4-SNC and is the answer not in the manual?

Questions and answers

Subscribe to Our Youtube Channel

Summary of Contents for Johnson Controls F4-SNC

  • Page 1 12 outputs. The first two numbers of the product code number represent the number of inputs (SNC25151-0x/ The Facility Explorer SNC Series (F4-SNC) are Ethernet- x) and the next two numbers represent the number based, supervisory controllers that connect Building of outputs (SNC25151-0x/x).
  • Page 2 See Connecting input and output A ports. terminals for more information. USB-1 (top port): Any Johnson Controls Two active Ethernet ports, 1000/100/10 approved USB device can be connected to Mbps; 8-pin RJ45 connector, labeled ETH-1 the top port. (top) and ETH-2 (bottom).
  • Page 3: Installation

    • Fasteners option - Three fasteners appropriate for the transformer does not obstruct ventilation of the SNC mounting surface: housing. - #8 screws - North America - M4 screws - Europe Dimensions Figure 3: SNC mounting dimensions, in. (mm) F4-SNC Installation Guide...
  • Page 4: Wiring Overview

    America, use a Class 2, 24 VAC power supply with a 50 VA minimum output. Outside North America, use a 24 VAC SELV (safety extra-low voltage) transformer at the appropriate rating. The minimum input voltage for the SNC to operate properly is 20 VAC. F4-SNC Installation Guide...
  • Page 5 -couper entièrement l'alimentation wire colors may be different on transformers not de l'équipement. Tout contact avec des composants manufactured by Johnson Controls. conducteurs de tensions dangereuses risque • Verify that transformer phasing is uniform across the d'entraîner une décharge électrique et de provoquer devices.
  • Page 6: Connecting The Power Source

    Table 3 ). The connections are HOT and COM (common). Note: Power supply wire colors may be different on transformers not manufactured by Johnson Controls. Follow the transformer manufacturer’s instructions and the project installation drawings. Set the FC EOL switch to the proper position. See...
  • Page 7: Terminal Functions, Ratings, Requirements, And Wiring Guidelines

    Description Brown wire (COM) Orange wire (24 VAC) Wires from Johnson Controls 24 VAC, Class Power Transformer Connecting input and output terminals The SNC25151-0x/x supports up to 40 hard-wired onboard I/O points, 25 inputs and 15 outputs.. The SNC1612x supports up to 28 hard-wired onboard I/O points, 16 inputs and 12 outputs.
  • Page 8: Input And Output Wiring Guidelines

    UI-# Qualified Sensors: 0–2k (Inputs) potentiometer, RTD (1k Nickel See Guideline A in Table 7. [Johnson Controls sensor], 1k Platinum, and A99B Silicon Temperature Sensor) NTC Sensor (10k Type L, 10k JCI Type II, 2.252k Type II). Binary Input - Dry Contact Maintained Mode See Guideline A in Table 7.
  • Page 9 Ohm may not operate as intended for Current Mode applications. Analog Output Signal Common for all Analog OUT terminals Note: All Analog AO-C# AO-C# Same as (Analog) AO-#. terminals share a common, which is isolated from all other commons. F4-SNC Installation Guide...
  • Page 10 All Configurable Outputs defined as Binary Outputs are isolated from all other commons, including other Configurable Output commons. The following table defines cable length guidelines for the various wire sizes that can be used for input and output wiring. F4-SNC Installation Guide...
  • Page 11: Maximum Cable Length Versus Load Current

    FC Bus Signal References and 15 VDC Common FC Bus retractable cable or 24 AWG 3-pair (port) • 15 VDC Power for Wireless Commissioning CAT 3 Cable <30.5 m (100 ft) • Converter or ZFR1811 Wireless Router F4-SNC Installation Guide...
  • Page 12: Termination Diagrams

    SA Bus cables. Termination diagrams A set of Johnson Controls termination diagrams provides See the figures in this section for the applicable details for wiring inputs and outputs to the controllers. termination diagrams.
  • Page 13 Type of input/ Type of field device Termination diagrams output Temperature Sensor Voltage Input - External Source Voltage Input - Internal Source Voltage Input (self-powered) Current Input - External Source (isolated) Current Input - Internal Source (2-wire) F4-SNC Installation Guide...
  • Page 14 Current Input - External Source (in loop) Feedback from EPP-1000 Dry Contact (binary input) UI or BI 0–10 VDC Output to Actuator CO or AO (external source) 0–10 VDC Output to Actuator CO or AO (internal source) Current Output F4-SNC Installation Guide...
  • Page 15 24 VAC Triac output (switch low, BO or CO external source) Incremental control to actuator (switch high, internally sourced, Triac) Incremental control to actuator (switch low, internally sourced, Triac) Network Stat with Phone Jack SA Bus (Fixed Address = 199) F4-SNC Installation Guide...
  • Page 16: Setting The Eol Switch

    Network Sensor at address 199. If there is no connected Network Sensor, the startup of this default state is delayed by 30 seconds as the controller attempts to establish connection with the sensor.For more details F4-SNC Installation Guide...
  • Page 17: Troubleshooting

    Table 10 describes each LED on the device. The normal states are in bold. A flicker has a fast blink rate faster than one second and a flash has a much slower blink rate of one second. F4-SNC Installation Guide...
  • Page 18 SNC. Non-qualified adapters do not function with the SNC. No USB device is connected On Steady = end-of-line termination is enabled for the Field Bus connection Yellow Off Steady = indicates the end of line termination network is disabled F4-SNC Installation Guide...
  • Page 19: Reset Button

    • the device is unresponsive or is in a frozen state • the device fails to take a code download from SCT Important: If you are unsure about whether to use the Recovery operation, contact Johnson Controls technical support. When you press the Recovery button, the action that takes place depends on whether this is the first time or a subsequent time you pressed the button.
  • Page 20 One FC Bus Supports up to 50 MS/TP controllers on a single FC Bus segment for the SNC25151-0 or SNC16121-0. Number of devices One FC Bus Supports up to 4 MS/TP controllers on a single FC Bus segment. for the SNC25151-0x/ x or SNC16121-04. F4-SNC Installation Guide...
  • Page 21 16 inputs/12 outputs 16 inputs/12 outputs Maximum objects in 2500 2500 2500 2500 device Number of site devices including self Maximum allowed devices across all integrations. For example, MS/TP+IP. Ethernet BACnet/IP maximum trunks BACnet/IP maximum devices per trunk F4-SNC Installation Guide...
  • Page 22 • 4 CO • 4 CO • 4 CO Ethernet Port Field Controller (FC) Bus Devices per FC Bus/ Trunk SA Bus USB Ports Supported • FX Server software type of • FX80 Supervisory Controller parent server F4-SNC Installation Guide...
  • Page 23: Accessories Ordering Information

    If you replace a SNC for any reason or add a new SNC to a site, you must update the site pairing to ensure that the new SNC is recognized and can communicate. Refer to F4-SNC Commissioning Guide (LIT-12013520) for more information.
  • Page 24 Canada: UL Listed, File E107041, CCN PAZX7, CAN/CSA C22.2 No. 205, Signal Equipment; Industry Canada Compliant, ICES-003 Europe: Johnson Controls declares that this product is in compliance with the essential requirements and other relevant provisions of the EMC Directive. Australia and New Zealand: RCM Mark, Australia/NZ Emissions Compliant...
  • Page 25 United States: UL Listed, File E107041, CCN PAZX, UL 916, Energy Management Equipment; FCC Compliance Compliant to CFR47, Part 15, Subpart B, Class A Canada: UL Listed, File E107041, CCN PAZX7, CAN/CSA C22.2 No. 205, Signal Equipment; Industry Canada Compliant, ICES-003 F4-SNC Installation Guide...
  • Page 26: North American Emissions

    Your use of this product constitutes an agreement to such terms. © 2020 Johnson Controls. All rights reserved. All specifications and other information shown were current as of document revision and are subject to change without notice. www.johnsoncontrols.com...

Table of Contents