General Data, 400 V Converters - Siemens SINAMICS G120 Installation Manual

Power modules, ip20 / push-through technology (pt)
Hide thumbs Also See for SINAMICS G120:
Table of Contents

Advertisement

Technical data
6.5 400 V converters
6.5.1

General data, 400 V converters

Property
Line voltage
Line supply configurations
Line impedance
Power factor λ
Output voltage
Input frequency
Output frequency
Inrush current
Overvoltage category ac-
cording to EN 61800-5-1
Pulse frequency
Short-circuit current
(SCCR) and branch protec-
tion
Braking methods
Degree of protection ac-
cording to EN 60529
Protection class according
to EN 61800-5-1
Touch protection according
to EN 50274
Cooling in compliance with
EN 60146
Safety Integrated
88
Version
FSA ... FSC
380 V ... 480 V 3 AC ± 10%
FSD ... FSG
380 V ... 480 V 3 AC ± 10% (in operation -20% < 1 min)
Grounded TN/TT line supplies or non-grounded IT line supplies
Permissible line supplies (Page 46)
FSA ... FSC
1% ≤ Uk < 4%, for values smaller than 1%, we recommend a line reactor, or
a Power Module with the next higher power rating.
FSD ... FSG
No restrictions
FSA ... FSC
0.7 without line reactor for Uk ≥ 1%
0.85 with line reactor for Uk < 1%
FSD ... FSG
> 0.9
0 V 3 AC ... 0.95 x input voltage (max.)
50 Hz ... 60 Hz, ± 3 Hz
0 ... 550 Hz, depending on the control mode
< LO base load input current
III for line supplies
Factory setting
4 kHz for devices with an LO base load power < 110 kW
2 kHz for devices with an LO base load power ≥ 110 kW
Can be adjusted in 2 kHz steps as follows:
2 kHz ... 16 kHz for devices with an LO base load power < 55 kW
2 kHz ... 8 kHz for devices with an LO base load output of 55 kW ... 250 kW
If you increase the pulse frequency, the converter reduces the maximum output current.
Current reduction as a function of the pulse frequency (Page 98)
Maximum permissible line short-circuit current ≤ 100 kA rms
Branch protection and short-circuit strength according to UL and IEC
(https://support.industry.siemens.com/cs/ww/en/view/109479152)
DC braking, compound braking, dynamic braking with integrated braking chopper
IP20
IP55
PT devices outside the control cabinet
The converters are devices with protection class I
DGUV regulation 3 when used for the intended purpose
Forced air cooling AF
See function manual "Safety Integrated"
"Safety Integrated" function manual
(https://support.industry.siemens.com/cs/ww/en/view/109751320)
Hardware Installation Manual, 01/2020, A5E33294624B AL