Technical data
6.5 400 V converters
6.5.1
General data, 400 V converters
Property
Line voltage
Line supply configurations
Line impedance
Power factor λ
Output voltage
Input frequency
Output frequency
Inrush current
Overvoltage category ac-
cording to EN 61800-5-1
Pulse frequency
Short-circuit current
(SCCR) and branch protec-
tion
Braking methods
Degree of protection ac-
cording to EN 60529
Protection class according
to EN 61800-5-1
Touch protection according
to EN 50274
Cooling in compliance with
EN 60146
Safety Integrated
88
Version
FSA ... FSC
380 V ... 480 V 3 AC ± 10%
FSD ... FSG
380 V ... 480 V 3 AC ± 10% (in operation -20% < 1 min)
Grounded TN/TT line supplies or non-grounded IT line supplies
Permissible line supplies (Page 46)
FSA ... FSC
1% ≤ Uk < 4%, for values smaller than 1%, we recommend a line reactor, or
a Power Module with the next higher power rating.
FSD ... FSG
No restrictions
FSA ... FSC
0.7 without line reactor for Uk ≥ 1%
0.85 with line reactor for Uk < 1%
FSD ... FSG
> 0.9
0 V 3 AC ... 0.95 x input voltage (max.)
50 Hz ... 60 Hz, ± 3 Hz
0 ... 550 Hz, depending on the control mode
< LO base load input current
III for line supplies
Factory setting
4 kHz for devices with an LO base load power < 110 kW
•
2 kHz for devices with an LO base load power ≥ 110 kW
•
Can be adjusted in 2 kHz steps as follows:
2 kHz ... 16 kHz for devices with an LO base load power < 55 kW
•
2 kHz ... 8 kHz for devices with an LO base load output of 55 kW ... 250 kW
•
If you increase the pulse frequency, the converter reduces the maximum output current.
Current reduction as a function of the pulse frequency (Page 98)
Maximum permissible line short-circuit current ≤ 100 kA rms
Branch protection and short-circuit strength according to UL and IEC
(https://support.industry.siemens.com/cs/ww/en/view/109479152)
DC braking, compound braking, dynamic braking with integrated braking chopper
IP20
IP55
PT devices outside the control cabinet
The converters are devices with protection class I
DGUV regulation 3 when used for the intended purpose
Forced air cooling AF
See function manual "Safety Integrated"
"Safety Integrated" function manual
(https://support.industry.siemens.com/cs/ww/en/view/109751320)
Hardware Installation Manual, 01/2020, A5E33294624B AL
Power Module PM240-2