Output Reactor - Siemens SINAMICS G120 Installation Manual

Power modules, ip20 / push-through technology (pt)
Hide thumbs Also See for SINAMICS G120:
Table of Contents

Advertisement

Accessories

8.10 Output reactor

8.10
Output reactor
Output reactors reduce the voltage stress on the motor windings and the load placed on the
converter as a result of capacitive recharging currents in the cables.
When using a output reactor, observe the following restrictions:
● The output frequency must not exceed 150 Hz.
● The pulse frequency must not exceed 4 kHz.
NOTICE
Damage to the output reactor by exceeding the maximum pulse frequency
The maximum permissible pulse frequency when using the output reactor is 4 kHz. The
output reactor can be damaged if the pulse frequency is exceeded.
• When using an output reactor, the pulse frequency of the Power Module must not be
NOTICE
Damage to the output reactor if it is not activated during commissioning
The output reactor may be damaged if it is not activated during commissioning.
• Activate the output reactor during commissioning via the parameter specified by the
• Activate the output reactor during commissioning according to the electric specifications.
Mounting position
144
higher than 4 kHz.
converter manufacturer.
Hardware Installation Manual, 01/2020, A5E33294624B AL
Power Module PM240-2

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Sinamics pm240-2

Table of Contents