Siemens SINAMICS G120 Installation Manual page 129

Power modules, ip20 / push-through technology (pt)
Hide thumbs Also See for SINAMICS G120:
Table of Contents

Advertisement

Assignment tables
Power Module, 400 V
Frame
size
FSB
FSC
FSD
FSE
FSF
FSG
Two 132 kW filters in parallel are required.
*)
If the expected input power exceeds the rating of the largest available filter, and a custom
solution is not desired, then two or more filters can be wired in parallel. In this mode of
operation, it is recommended to use filters with equal power ratings to ensure proper current
sharing.
NOTICE
Line harmonic filters for Power Modules with 160 kW, 200 kW and 250 kW
The following combinations must not be used with u/f control.
• Power Module 160 kW with LHF: UAC:FN3440160118E2FAJXX
• Power Module 200 kW with LHF: UAC:FN3440200118E2FAJXX
• Power Module 250 kW with 2 LHF in parallel: UAC:FN3440132118E2FAJXX
When you use one of this combinations only the following settings of p1300 are allowed:
• P1300 = 20,
• P1300 = 21
• P1300 = 22
• P1300 = 23
Power Module PM240-2
Hardware Installation Manual, 01/2020, A5E33294624B AL
Article number
6SL3210-1PE21-4 . L0
6SL321 . -1PE21-8 . L0
6SL3210-1PE22-7 . L0
6SL321 . -1PE23-3 . L0
6SL3210-1PE23-8 . L0
6SL3210-1PE24-5 . L0
6SL3210-1PE26-0 . L0
6SL321 . -1PE27-5 . L0
6SL3210-1PE28-8 . L0
6SL321 . -1PE31-1 . L0
6SL3210-1PE31-5 . L0
6SL3210-1PE31-8 . L0
6SL3210-1PE32-1 . L0
6SL321 . -1PE32-5 . L0
6SL3210-1PE33-0 . L0
6SL3210-1PE33-7 . L0
6SL3210-1PE34-8 . L0
Line harmonics filter
Power [kW]
Article number
5.5
UAC:FN34406112E2XXJRX
7.5
UAC:FN34408112E2XXJRX
11
UAC:FN344011113E2FAJRX
15
UAC:FN344015113E2FAJRX
18.5
UAC:FN344019113E2FAJRX
22
UAC:FN344022115E2FAJRX
30
UAC:FN344030115E2FAJRX
37
UAC:FN344037115E2FAJRX
45
UAC:FN344045115E2FAJRX
55
UAC:FN344055115E2FAJRX
75
UAC:FN344075116E2FAJRX
90
UAC:FN344090116E2FAJRX
110
UAC:FN3440110118E2FAJRX
132
UAC:FN3440132118E2FAJXX
160
UAC:FN3440160118E2FAJXX
200
UAC:FN3440200118E2FAJXX
250
UAC:FN3440132118E2FAJXX
Accessories
8.6 Line harmonics filter
*)
127

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Sinamics pm240-2