Siemens SINAMICS G120 Installation Manual page 130

Power modules, ip20 / push-through technology (pt)
Hide thumbs Also See for SINAMICS G120:
Table of Contents

Advertisement

Accessories
8.6 Line harmonics filter
Clearances to other devices
Line harmonics filters are best installed as close as possible to the non-linear load. Ideally
they are mounted next to the converter inside the electrical cabinet.
In order to ensure sufficient air flow, keep a clearance of minimum 150 mm above and below
the filter to walls or other components.
It must be ensured that the environmental temperature is kept below 45 °C with appropriate
thermal management (e.g. cabinet cooling). Filter operation in environments with higher
temperatures require a temperature derating.
128
Hardware Installation Manual, 01/2020, A5E33294624B AL
Power Module PM240-2

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Sinamics pm240-2

Table of Contents