Technical data
6.4 200 V converters
Table 6- 6
PM240-2, PT, frame size C, 200 V ... 240 V 1 AC / 3 AC
Article No. without filter
Article No. with filter
LO base load power
1 AC LO base load input current
3 AC LO base load input current
LO base load output current
HO base load power
1 AC HO base load input current
3 AC HO base load input current
HO base load output current
Fuse according to IEC
Fuse according to UL, class J
Power loss
Required cooling air flow
Weight without filter
Weight with filter
approx. 0.09 kW through the heat sink
1)
Table 6- 7
PM240-2, IP 20, frame size C, 200 V ... 240 V 3 AC
Article No. without filter
Article No. with filter
LO base load power
LO base load input current
LO base load output current
HO base load power
HO base load input current
HO base load output current
Fuse according to IEC
Fuse according to UL, class J
Power loss
Required cooling air flow
Weight without filter
Weight with filter
82
6SL3211-1PB21-8UL0
6SL3211-1PB21-8AL0
4 kW
43.0 A
22.8 A
17.5 A
3 kW
37.5 A
17.7 A
13.6 A
3NA3820 (50 A)
50 A
0.18 kW
1)
18.5 l/s
5.9 kg
6.2 kg
6SL3210-1PC22-2UL0
6SL3210-1PC22-2AL0
5.5 kW
28.6 A
22.0 A
4 kW
22.8 A
17.5 A
3NA3820 (50 A)
50 A
0.2 kW
18.5 l/s
5.0 kg
5.2 kg
6SL3210-1PC22-8UL0
6SL3210-1PC22-8AL0
7.5 kW
36.4 A
28.0 A
5.5 kW
28.6 A
22.0 A
3NA3820 (50 A)
50 A
0.26 kW
18.5 l/s
5.0 kg
5.2 kg