3.2.2

Cables

Cables with a high level of interference and cables with a low level of interference are
connected to the converter:
● Cables with a high level of interference:
– Cable between the line filter and converter
– Motor cable
– Cable at the converter DC link connection
– Cable between the converter and braking resistor
● Cables with a low level of interference:
– Cable between the line and line filter
– Signal and data cables
Cable routing inside the cabinet
● Route the power cables with a high level of interference so that there is a minimum
clearance of 25 cm to cables with a low level of interference.
If the minimum clearance of 25 cm is not possible, insert separating metal sheets
between the cables with a high level of interference and cables with a low level of
interference. Connect these separating metal sheets to the mounting plate to establish a
good electrical connection.
● Cables with a high level of interference and cables with a low level of interference may
only cross over at right angles:
● Keep all of the cables as short as possible.
● Route all of the cables close to the mounting plates or cabinet frames.
● Route signal and data cables - as well as the associated equipotential bonding cables -
parallel and close to one another.
● Twist incoming and outgoing unshielded individual conductors.
Alternatively, you can route incoming and outgoing conductors in parallel, but close to
one another.
● Ground any unused conductors of signal and data cables at both ends.
● Signal and data cables must only enter the cabinet from one side, e.g. from below.
● Use shielded cables for the following connections:
– Cable between the converter and line filter
– Cable between the converter and output reactor or sine-wave filter
Power Module PM240-2
Hardware Installation Manual, 01/2020, A5E33294624B AL
3.2 EMC-compliant installation of a machine or system